Specification and Operating Instructions

KLTH43 Temperature and Humidity

 

Controller

Description

Installation

The KLTH43 is a temperature and humidity digital controller. The 
temperature control can be ON-OFF, neutral zone and refrigeration 
modes. It is possible to set a second temperature probe for 
defrosting control. Humidity control can be ON-OFF and neutral 
zone modes. The humidity probe can be 0-1V, 0-3V KLSH03 and   4-
20mA types.

The model reference is given by: KLTH43 - YZ

Each sufix can take the following values:

Y

Supply Voltage

230=230VAC, 115=115VAC

Z

Temp. Units

C=ºC, F=ºF

• 




Model references

NOTE: Unit must be mounted away from vibration, impacts, water 
and corrosive gases.

Cut hole in panel 131 x 101 mm (5.15 x 3.97 inches).

 Remove the rear cover to wire the unit.
 The wiring diagram is shown in the unit label.
 Apply silicone (or rubber gasket) around the perimeter of the hole 

to prevent leakage.

 Insert the unit in the panel hole.
 Replace the rear cover.
 Place removable fitting clips from the back of the until it is secured 

to the panel.

 Fit the clip in the panel and then press to fit the other side in the 

unit.

Temperature Probe 1 (Sd1) in terminals 18 - 17
Temperature Probe 2 (Sd2) in terminals 19 - 17
Humidity Probe (SH) in terminals 20-21-17

 Note: DO NOT INSTALL PROBE CABLES NEAR POWER 

CABLES.

Technical Data

Storage temperature

-20ºC to 80ºC  (

-

4 to 176ºF)

Operating temperature

0ºC to 70ºC (32 to 158ºF)

Temperature probe

PTC1000 (25ºC - 1000 Ohm)

Temperature probe range

-50ºC to 150ºC (-58 to 302ºF) 

Temperature accuracy

Better than 0,5

Temperature resolution

Humidity probe

0-1V, 0-3V KLSH03  4-20mA

Humidity  probe range

0 to 100% RH

Humidity  accuracy

Better than 5

Humidity  resolution

1% (3 digits)

Supply voltages

115 VAC10%, 230 VAC10%

Supply powers

7VA (230V)

% of full scale

0.1º (3 digits)

,

% of full scale

Displays

3-digit and sign (x2)

Outputs

SPDT relay 250Vac  8A RL

Dimensions

134x105x61mm (5.3x4.1x2.4 in)

Front Protection

IP65

Wiring Diagram

• Dependent ON/OFF control

If rh8=ono and rh0=dEP, output 3 works as in Independent ON/OFF 
control, but output 4 works as follows: 
If ch3=dir, output 4 will connect when HS >=

 

Sh1+Sh2+rh2 and will 

disconnect when HS <= Sh1+Sh2.

If ch3=Inv, output 4 will connect when HS <=

 

Sh1+Sh2-rh2 and will 

disconnect when HS >= Sh1+Sh2.
ch1 is the minimum stop time.

• Neutral zone control

If rh8 = NEu output 3 connects when HS >= Sh1+rh3 and 
disconnects when HS <= Sh1, while output 4 connects when Hs1 
<= Sh1-rh3 and disconnects when HS >= Sh1.

• Control with probe errors

If reading of humidity probe fails the output 3 works following 10 
minutes cycles, with a percentage of connection time given by Ch4. 
Output 4 is carried out in the same way with parameter Ch5.

• Humidity alarms

If HS >= Sh1+Ah1, the controller will indicate maximum humidity 
alarm for (AHH) and the alarm will remain activated until HS <= 
Sh1+Ah1-Ah0.
If HS <= Sh1-Ah2, the controller will activate minimum humidity 
alarm for (ALH), and it will remain activated until HS >= Sh1-Ah2-
Ah0.
Program Ah3 to indicate the alarm check time between alarm 
event and indication of an alarm event. The alarm is indicated by 
a message on the display and activating the alarm output if 
present (alarm can be silenced pressing UP+DOWN keys or 
CLEAR in the IR remote control).

• Probe options

Set Ph1 to select if the decimal point is shown or not in the 
display.
Set Ph2 to set the probe type (0-1V, CRPH03 or 4-20mA).
If a 4-20mA probe is used, use Ph3 to set the humidity value 
for 4mA and Ph4 to set the value for 20mA.

H1,H2,H3 are general parameters that can be accessed from 
both temperature and humidity parameters.
Setting H1 to yES the set points (St1,St2,Sh1,Sh2) cannot be 
changed. To unblock this protection, press SET T or SET H for 8 
seconds and introduce the code in the same way as is done when 
entering parameters.
H2 sets the communication address for the controller.
H3 sets the access code to parameters.

The four 

OUT 

leds indicate the of the four outputs (when the 

correspondent led is ON the output is connected and when the 
led is OFF the output is disconnected).

In normal operation, the left display will show the temperature 
measured by probe 1 and the right display the relative 
humidity. In order to display the temperature measured by 
probe 2 press SET T + UP keys.

In case of alarm or error, the following messages can be 
shown:
• 

Err 

= Memory reading error

• 

ErP 

= Error in the temperature probe 2

• AHt 

 

= High temperature alarm (probe 1)

• ALt 

 

= Low temperature alarm (probe 1)

• AHh 

 

= High humidity alarm

• ALh 

 

= Low humidity alarm

• o

oo 

= Open Probe Error

• ---

 

= Short Circuit Probe Error

Clean the surface of the display controller with a soft and damp 
cloth. Never
 use abrasive detergents, petrol, alcohol or solvents.

All repairs must be made by authorised personnel.

If the probe is not placed in the exact point to control, use a 
standard hygrometer to determine the offset and set it by Ph0.

General parameters

Led indication and display messages

Maintenance, cleaning and repair

After final installation of the unit, no routine maintenance is 
required.

Humidity

Time

Sh1+Sh2+rh2

Sh1+Sh2

Output 4 ON

ch1

Humidity

Time

Sh1+Sh2

Sh1+Sh2-rh2

Output 4 ON

ch1

Humidity

Humidity

Sh1+Ah1

Sh1+Ah1-Ah0

High Alarm ON

Sh1-Ah2

Sh1-Ah2+Ah0

Low Alarm ON

Humidity

Time

Sh1+rh3

Sh1

Output 4 ON

Sh1-rh3

Output 3 ON

1   2   3   4   5   6   7   8   9   10 11 12 13 14

15 16 17 18 19 20 21 

SUPPLY

RX  TX  GND                IN   VCC

OUT4            OUT3            OUT2            OUT1

Sd1  Sd2    SH

%H

E L E C T R Ó N I C A

E L E C T R Ó N I C A

ETDT1076I_090319

 Electrónica Keld, S.L. 
 Pol.Ind. Empresarium. C/Lentisco 15
 50720 - La Cartuja Baja, ZARAGOZA
 Spain

Phone: +34 976 429 099 

Fax:+34 976 593 532 

E-mail: [email protected] 

Web: http://www.keld.es 

ETDT1076I_090319

 Electrónica Keld, S.L. 
 Pol.Ind. Empresarium. C/Lentisco 15
 50720 - La Cartuja Baja, ZARAGOZA
 Spain

Phone: +34 976 429 099 

Fax:+34 976 593 532 

E-mail: [email protected] 

Web: http://www.keld.es 