List of humidity parameters

  

Description

Units

Range

Sh1  Humidty set point 1

%RH

rh4 to rh6

Sh2 Humidty set point 2

%RH

rh5 to rh7

rh0 Sh1 and Sh2 dependency

Range

Ind / dEP

rh1 Differencial for Sh1

%RH

0.1 to 30.0

rh2 Differencial for Sh2

%RH

0.1 to 30.0

rh3 Band differencial

%RH

0.1 to 30.0

rh4 Minimum  value for Sh1

%RH

0 to rh6

rh5 Minimum  value for Sh2

%RH

0 to rh7

rh6 Maximum value for Sh1

%RH

rh4 to 100

rh7 Maximum value for Sh2

%RH

rh5 to 100

rh8 Operation mode

Range

ono/nEU

Ah0 Alarm differencial

%RH

0.1 to 20.0

Ah1 Maximum probe alarm

%RH

0.1 to 99.9

Ah2 Minimum probe alarm

%RH

0.1 to 99.9

Ah3 Alarm check time

hh:mm

0.0 to 18.0

ch0 Minimum stop time output 3

Minutes

0 to 240

ch1 Minimum stop time output 4

Minutes

0 to 240

ch2 Operation output 3

Range

Dir/Inv

ch3 Operation output 4

Range

Dir/Inv

ch4 Default operation output 3

%ON

0 to 100

ch5 Default operation output 4

%ON

0 to 100

Ph0 Hum. probe adjustment

%RH

-20 to 20

Ph1 Decimal point

Option

no/yES

Ph2 Humidity Probe type

Range

1V/3V/420

Ph3 Value for 4mA

%RH

0.0 to 100

Ph4 Value for 20mA

%RH

0.0 to 100

H0

Set default settings

Command

H1

Keypad protection

Option

NO/YES

H2

Communication setup

Numeric

0 to 999

H3

Access code to parameters

Numeric

0 to 999

Humidity parameter programming

Follow the same steps as when adjusting temperature 
parameters but using the SET H key. 

Humidity control process

• Independent ON/OFF control

If rh8=ono and rh0=Ind, each output is associated to a particular 
Set.
If ch2=dir, output 3 will connect when HS >=

 

Sh1+rh1 (where HS 

is the   humidity measured) and will disconnect when HS <= Sh1.

ch0 is the minimum stop time. Once the output is disconnected, it 
is not connected again until ch0 minutes later.
If ch2=Inv, output 3 will connect when HS <=

 

Sh1-rh1 and will 

disconnect when HS >= Sh1.

The output 4 is handled in the same manner but controlled by 
Sh2, using

 

rh2 as differential, ch3 as indicator of direct or reverse 

connection, and ch1 as minimum stop time.

List of temperature parameters

  

Description

Units

Range

St1  Temperature set point 1

Degrees

rt4 to rt6

St2 Temperature set point 2

Degrees

rt5 to rt7

rt0

St1 and St2 dependency

Range

Ind / dEP

rt1

Differencial for St1

Degrees

0.1 to 20.0

rt2

Differencial for St2

Degrees

0.1 to 20.0

rt3

Band differencial

Degrees

0.1 to 20.0

rt4

Minimum value for St1

Degrees

-99.9 to rt6

rt5

Minimum value for St2

Degrees

-99.9 to rt7

rt6

Maximum value for St1

Degrees

rt4 to 302

rt7

Maximum value for St2

Degrees

rt5 to 302

rt8

Operation mode

Range

ono/rEF/nEU

dt0

Defrosting type

Range

fRES/InV

dt1

Max. defrosting temperature Degrees

-99.9 to 302

dt2

Max. defrosting time

Minutes

0 to 240

dt3

Defrosting interval time

hh:mm

0.0 to 18.0

dt4

Defrosting displayed temp.

Range

off/on/-d-

At0 Alarm differencials

Degrees

0.1 to 20.0

At1 Maximum probe 1 alarm

Degrees

0.1 to 99.9

At2 Minimum probe 1 alarm

Degrees

0.1 to 99.9

At3 Alarm check time

hh:mm

0.0 to 18.0

ct0

Minimum stop time output 1

Minutes

0 to 240

ct1

Minimum stop time output 2

Minutes

0 to 240

ct2

Operation output 1

Range

DIr/Inv

ct3

Operation output 2

Range

DIr/Inv

ct4

Default operation output 1

%ON

0 to 100

ct5

Default operation output 2

%ON

0 to 100

ct6

Continuous cycle time

Minutes

0 to 240

Pt0 Temp. probe adjustment

Degrees

-20.0 to 20.0

Pt1 Decimal point

Option

no/yES

Pt2 Temperature units

Range

ºC/ºF

Pt3 Number of temp. probes

Range

1 / 2

H0

Set default settings

Command

H1

Keypad protection

Option

no/yES

H2

Communication setup

Numeric

0 to 999

H3

Access code to parameters

Numeric

0 to 999

Temperature parameter programming

Set Points (St1,St2) are the only parameters the user can
access without code protection.

•Press SET T. Current value of St1 appears flashing and led OUT 1 
flashes.
•The value can be modified with the UP and DOWN arrows.
•Press SET again to confirm St1. Current value of St2 appears 
flashing and led OUT 2 flashes.
•The value can be modified with the UP and DOWN arrows.
•Press SET to enter St2 value and exit.

Access to all code protected parameters.

•Press SET T for 8 secs. The access code value 0 is shown on the 
display (unit comes with code set at 0 from factory).
• Select the correct code with the UP and DOWN arrows.
•Press SET T to enter the code. If the code is correct, the first 
parameter label is shown on the display (St1).
• Move to the desired parameter with the UP and DOWN.
•Press SET T to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
•Press SET to enter the value.
• Repeat until all necessary parameters are modified.
•Press SET and DOWN at the same time to quit programming or 
wait one minute and the display will automatically exit programming 
mode.

*The keyboard code can be reset to ZERO by turning
off the controller and turning it on again while
keeping the SET T   key depressed.

Defrosting is performed at time periods indicated by dt3. If dt3 is 
zero, no   defrosting is performed periodically. Defrosting is 
deactivated when TS2 (temperature of probe 2) reaches dt1 value 
or when the maximum defrosting time dt2 is reached.
Defrosting can also be activated and deactivated from the keypad, 
pressing the UP arrow for 8 seconds, or IR remote control. 
Defrosting can not be activated if a continuous cold cycle is 
activated, unit is in auxiliary adjustment mode, TS2 >=dt1 or dt2=0.
With dt4 parameter we can choose that during the defrosting and 
one hour after a message -d- is displayed until the temperature 
raises the initial defrosting temperature. It is also possible to show 
the initial temperature during the defrosting or to show the actual 
temperature all the time.

• Continuous cold cycle

A continuous cold cycle maintains the compressor (output 1) in 
operation for a period of time given by ct6. These cycles are 
activated from the keypad, keeping the DOWN arrow pressed for 8 
seconds, and end when the time is finished or an order is given from 
the keypad (pressing DOWN for 8 seconds again). The cycle will 
not commence if the unit is in heat control mode or i auxiliary 
adjusting mode (due to memory failure) or if defrosting is activated.

• Neutral zone control

If rt8 = NEu output 1 connects when TS1 >= St1+rt3 and 
disconnects when TS1 <= St1, while output 2 connects when TS1 
<= St1-rt3 and disconnects when TS1 >= St1.

• Control with probe errors

If reading of probe 1 fails the output 1 works following 10 minutes 
cycles, with a percentage of connection time given by Ct4. Output 2 
is carried out in the same way with parameter Ct5.
If reading of probe 2 fails, the defrosting ends by time.

• Temperature alarms

If TS1 >= St1+At1, the thermostat will indicate maximum 
temperature alarm for probe1 (Aht) and the alarm will remain 
activated until temperature TS1 <= St1+At1-At0.
If TS1 <= St1-At2, the thermostat will activate minimum 
temperature alarm for probe 1 (ALt), and it will remain activated 
until temperature TS1 >= St1-At2-At0.
Program At3 to indicate the alarm check time between alarm 
event and indication of an alarm event. The alarm is indicated by 
a message on the display and activating the alarm output if 
present (alarm can be silenced pressing SETT+DOWN keys or 
CLEAR in the IR remote control).

• Probe options

Set Pt1 to select if the decimal point is shown or not in the 
display.
Set Pt2 to set temperature units (Celsius of Fahrenheit).

Set Pt3 to select if 1 or 2 temperature probes are used.

If the probe is not placed in the exact point to control, use a 
standard thermometer to determine the offset and set it by Pt0.

Set default settings

• Access parameter H0 as explained

0 will appear.

• Press SET T or SET H for 8 seconds. Pro

 

will appear on the display 

if the Set Point is correct and Epr will appear if it is not correct. 
• Press SETT+DOWN or SETH+DOWN to exit or wait 1 minute.

Temperature control process

• Independent ON/OFF control

If rt8=ono and rt0=Ind, each output is associated to a particular Set.
If ct2=dir, output 1 will connect when TS1 >=

 

St1+rt1 (where TS1 is 

the   temperature of probe 1) and will disconnect when TS1 <= St1.

ct0 is the minimum stop time. Once the output is disconnected, it is 
not connected again until ct0 minutes later.
If ct2=Inv, output 1 will connect when TS1 <=

 

St1-rt1 and will 

disconnect when TS1 >= St1.

The output 2 is handled in the same manner but controlled by St2, 
using

 

rt2 as differential, ct3 as indicator of direct or reverse 

connection, and ct1 as minimum stop time.

• Dependent ON/OFF control

If rt8=ono and rt0=dEP, output 1 works as in Independent ON/OFF 
control, but output 2 works as follows: 
If ct3=dir, output 2 will connect when TS1 >=

 

St1+St2+rt2 (where 

TS1 is the   temperature of probe 1) and will disconnect when TS1 
<= St1+St2.

ct1 is the minimum stop time.
If ct3=Inv, output 2 will connect when TS1 <=

 

St1+St2-rt2 and will 

disconnect when TS1 >= St1+St2.

• Cooling control

If rt8=rEF the temperature is regulated by output 1 as in ON/OFF 
control, while defrosting is triggered by output 2.
Three defrosting methods are available:
1.Switch off the compressor (dt0=re)
2.Switch off the compressor and connect a heat resistor to output 2 
(dt0=re)
3.Switch on the compressor and connect an electro-valve to output 
2 to reverse the cycle (dt0=in)

Temperature

Time

St1+rt1

St1

Output 1 ON

ct0

Temperature

Time

St1

St1-rt1

Output 1 ON

ct0

Probe 1

Probe 1

Temperature

Time

St1+St2+rt2

St1+St2

Output 2 ON

ct1

Probe 1

Temperature

Time

St1+St2

St1+St2-rt2

Output 2 ON

ct1

Probe 1

Temperature

Time

St1+rt3

St1

Output 2 ON

Probe 1

St1-rt3

Output 1 ON

Temperature

St1+At1

St1+At1-At0

High Alarm ON

Probe 1

Temperature

St1-At2

St1-At2+At0

Low Alarm ON

Probe 1

Humidity

Time

Sh1+rh1

Sh1

Output 3 ON

ch0

Humidity

Time

Sh1

Sh1-rh1

Output 3 ON

ch0