If a remote input switch is connected to the F29 select yes to this question
by pressing the
button. Press the
(P)
button to lock your choice into memory
and to move to the next screen. You are then presented with a c
h
oice of 3
ways the remote input can be configured. Press the
(^)
or
(v)
buttons to
move from one option to the next.
The F29 houses 2 output relays. Relay 1 is normally used to control a
pump. Relay 2 is normally used as an alarm relay. Selecting yes to this
question allows you to configure the alarm relay to close its contacts
under various conditions. If you want to use the alarm relay press
(v)
and
then press
(P)
. Use the
(^)
or
(v)
buttons to move from one option to the
next.
CLOSED IF ANY FAULT DEVELOPS
Closed only on a genuine fault, open
at all other times.
CLOSED ONLY IF FLOW STOPS
Closed when the F29 detects no flow,
open at all other times.
CLOSED WHENEVER PUMP IS OFF
Closed when the pump is stopped,
o
pen when the pump is running.
CLOSED WHENEVER PUMP IS ON
Closed when the pump is running,
open when the pump is stopped.
CLOSED DURING PRE-START DELAY
Only closed while the pre-start delay
timer is running.
CLOSED ON FAULTS NOT IN CYC RUN
Closed on all faults except those
detected during cyclic running.
USE ALARM RELAY
USE REMOTE INPUT
Select this option if you are using a momentary contact switch or relay to
trigger the F29 and cause it to start. The remote switch can open its
contacts once the F29 has started or they can remain closed.
USE REMOTE FOR START ONLY
Select this option if you are using a 2 position high / low tank level switch to
control the F29. The F29 will be on when the remote switch is closed and off
when the remote switch is open.
USE REMOTE FOR START & STOP
This selection replicates the function of the
(R)
button. Momentary closing of
the remote contacts causes the F29 to reboot.
USE REMOTE FOR SYSTEM RESETTING