3 Installation
All rights reserved ©Kehua Data Co., Ltd.
35
No. Cable
Type
Cross-sectional
area
Outer
Diameter
Source
7
AC power
cable
Three-core (L, N and
PE) outdoor copper
cable
4
~
6 mm
2
12.6-13.9
mm
Purchased
by the
installer
8
PE cable
Single-core outdoor
copper cable
4
~
10 mm
2
N/A
Purchased
by the
installer
※
1 For CT communication connection with inverter.
※
2 For CAN/RS485, LAN, Meter, DRM communication connection with inverter.
※
3 For AUX communication connection with inverter
3.5.2 External Grounding Connection
The external grounding terminal is as shown in the
○
7 of Figure2-8.
The external grounding wire cannot replace the PE wire of AC output terminal, they must be
connected with ground reliably.
Step 1
Strip the insulation layer of grounding wire for about 7mm, insert the wire into OT terminal and
crimp them by crimping tool, the as shown in Figure3-24.
Figure3-24
Stripping diagram of external grounding wire (unit: mm)
Step 2
Connect the crimped grounding wire to the external grounding terminal, as shown in Figure3-25.