background image

INSTALLATION INSTRUCTIONS

R−410A, Two−Stage Split System Air Conditioner

421 01 6002 01

9

AIRFLOW SELECTION

Two−stage compressor operation requires two different
indoor airflow settings for proper operation.  This outdoor
unit is designed for use only with an indoor blower that can
be configured for separate low−stage and high−stage
airflow (CFM) levels.  Refer to Product Specifications
Sheets for recommended low−stage and high−stage
indoor airflow values.  Refer to indoor unit Installation
Instructions to set the indoor blower for the proper
low−stage and high−stage airflow values.

NOTE:  Optimal comfort, efficiency, and reliability will only
be achieved when the indoor airflow is properly set for
both low−stage and high−stage operation.

START−UP PROCEDURE

1.

Set indoor thermostat selector switch to OFF.

2.

Turn ON all electrical disconnect devices.

3.

Unit has a crankcase heater.  Energize the heater and
wait 24 hours before proceeding.

4.

Set indoor thermostat at desired temperature.  Be
sure setpoint is below indoor ambient temperature or
thermostat will not call for cooling.

5.

Set indoor thermostat selector switch to COOL.
Operate unit for minimum 25 minutes, then check the
system refrigerant charge.

REFRIGERANT CHARGE

NOTE: Charge in High−Stage only.

Outdoor units are shipped with a refrigerant charge to
match a specific  indoor coil and 15 feet (4.6m) of
refrigerant line. If shorter or longer refrigerant lines or a
different indoor coil are used, the charge will have to be
adjusted.

For different line lengths, add or remove charge based on
0.6 ounces (17g) charge per foot (305mm) of difference.
For example, a 25 foot (7.6m) line set is 10 feet (3m)
longer than the specified 15 feet (4.6m). Add 0.6 ounces
(17g) charge for each of the extra 10 feet (3m):

10 x 0.6 = 6.0 ounces additional charge

(3m x 17g = 51g additional charge)

This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. With an
indoor TXV, use the subcooling method to make final
charge adjustments:

NOTE: Only use subcooling charging method when

 outdoor ambient temperature is between 70

F and 100

F

(21

C and 38

C)

 indoor temperature is between 70

 and 80

F (21

C and

27

C)

 line set is less that 80 feet (24.4m).

1.

Operate unit a minimum of 25 minutes in
high−stage before checking charge.
NOTE: Outdoor unit has a 2−speed fan motor.
Motor will operate in low speed when outdoor
ambient temperature is below 82

°

F (28

C). Pull

one of the yellow low voltage wires off the fan
control and the unit will default to high speed fan for
servicing. Reconnect wire after servicing.

2.

Measure liquid service valve pressure by attaching
an accurate gauge to service port.

3.

Measure liquid line temperature by attaching an
accurate thermistor type sensor or electronic
thermometer to liquid line near outdoor coil.

4.

Refer to unit rating plate for required subcooling
temperature.

5.

Refer to Figure 11. Find the required liquid line
temperature where the rating plate subcooling
temperature intersects measured liquid service
valve pressure.

6.

If the measured liquid line temperature is higher
than the chart number, add refrigerant to lower the
measured temperature.

NOTE: When adding refrigerant, charge in liquid form,
using a flow restricting device, into the suction port.  If the
measured liquid line temperature is lower than the chart
number, reclaim refrigerant to raise the measured
temperature.
Tolerance is 

 3

°

F (

1.7

°C)

.

Содержание R?410A

Страница 1: ...ner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels W...

Страница 2: ...or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit...

Страница 3: ...les Wall 6 152mm 24 610mm Service Wall Wall Wall 6 152mm 6 152mm Post Wall Wall 18 457mm 18 457mm 18 457mm 18 152mm 6 152mm 6 152mm 6 152mm 18 457mm 18 457mm 18 457mm 18 457mm 24 610mm Service 24 610m...

Страница 4: ...ture is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roof a release must be obtained from the building owner to free the...

Страница 5: ...le avoiding unnecessary bends and turns Always insulate the entire suction line Both lines should be insulated when routed through an attic or when routed through an underground raceway When routing r...

Страница 6: ...are plugged from the factory Outdoor units are shipped with a refrigerant charge sealed in the unit Leave the service valves closed until all other refrigerant system work is complete or the charge w...

Страница 7: ...system is free of air and water Watch the vacuum gauge as the system is pulling down The response of the gauge is an indicator of the condition of the system refer to Figure 7 With no leaks in the sy...

Страница 8: ...mum to 253 volts maximum 60 Hz single phase Outdoor units are approved for use with copper conductors only Do not use aluminum wire Refer to unit rating plate for minimum circuit ampacity and circuit...

Страница 9: ...r example a 25 foot 7 6m line set is 10 feet 3m longer than the specified 15 feet 4 6m Add 0 6 ounces 17g charge for each of the extra 10 feet 3m 10 x 0 6 6 0 ounces additional charge 3m x 17g 51g add...

Страница 10: ...42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 SEQUEN...

Страница 11: ...d stage of the thermostat is calling for more capacity a starting advantage under low voltage conditions TROUBLESHOOTING Models are factory equipped with the Comfort Alert UltraTech Diagnostics device...

Страница 12: ...for Y2 to be energized test the voltage output at the plug with a DC voltmeter The reading here should be 4 to 18 volts If NOT unplug the harness from the module and check voltage at the DC Sol pins o...

Страница 13: ...age 4 Faulty metering device Check TXV bulb installation size location and contact Check if TXV is stuck closed or defective 5 Condenser coil is dirty 6 Liquid line restriction filter drier blocked 7...

Страница 14: ...pply and the compressor S terminal 3 Compressor start winding is damaged Check compressor motor winding resistance Yellow ALERT Flash Code 7 Open Run Circuit Current only in start circuit 1 Open circu...

Страница 15: ...HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Отзывы: