INSTALLATION INSTRUCTIONS

R−410A, Two−Stage Split System Air Conditioner

421 01 6002 01

5

Figure 3

Typical TXV Installation

TXV

SENSING
BULB

EQUALIZER
TUBE

ÉÉ

ÉÉ

ÉÉ

ÉÉ

8  O’CLOCK

4  O’CLOCK

STRAP

SENSING BULB
(EITHER SIDE)

SUCTION

TUBE

INDOOR

COIL

SUCTION
TUBE

LIQUID
TUBE

B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure
maximum efficiency and proper oil circulation.

Refer to Product Specifications and Long Line
Applications Guideline for line set sizing
.

If it is necessary to add refrigerant line in the field, use
dehydrated or dry, sealed, deoxidized, copper
refrigeration tubing. Do not use copper water pipe.

Do not remove rubber plugs or caps from copper tubing
until connections are ready to be made.

Be extra careful when bending refrigeration tubing.
Tubing can “kink” easily, and if this occurs, the entire
length of tubing must be replaced.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in per-
sonal injury and/or death.

Relieve pressure and recover all refrigerant before
servicing existing equipment, and before final unit
disposal. Use all service ports and open all flow−
control devices, including solenoid valves.

C. ROUTING AND SUSPENDING REFRIGERANT

LINES

Run refrigerant lines as straight and direct as possible,
avoiding unnecessary bends and turns. Always insulate
the entire suction line. Both lines should be insulated
when routed through an attic or when routed through an
underground raceway.

When routing refrigerant lines through a foundation or
wall, do not allow refrigerant lines to come in direct
contact with the building structure.  Make openings large
enough so that lines can be wrapped with extra insulation.
Fill all gaps with RTV caulk. This will prevent noise
transmission between the tubing and the foundation or
wall.

Along floor or ceiling joists, suspend refrigerant lines so
that they do not contact the building structure, water
pipes, or ductwork. Use insulated or suspension type
hangers. Metal straps must be at least 1” wide (25mm) to
avoid cutting into the tube insulation. Keep the liquid and
suction lines separate. Refer to Figure 4.

!

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in improp-
er product operation.

Do not leave system open to atmosphere any lon-
ger than absolutely required for installation. Inter-
nal system components − especially refrigerant
oils − are extremely susceptible to moisture con-
tamination. Keep ends of tubing sealed during
installation until the last possible moment.

Figure 4

Routing and Suspending Refrigerant Lines

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” (25mm) MIN

THROUGH THE WALL

SUSPENSION

Содержание R?410A

Страница 1: ...ner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels W...

Страница 2: ...or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit Locate unit...

Страница 3: ...les Wall 6 152mm 24 610mm Service Wall Wall Wall 6 152mm 6 152mm Post Wall Wall 18 457mm 18 457mm 18 457mm 18 152mm 6 152mm 6 152mm 6 152mm 18 457mm 18 457mm 18 457mm 18 457mm 24 610mm Service 24 610m...

Страница 4: ...ture is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roof a release must be obtained from the building owner to free the...

Страница 5: ...le avoiding unnecessary bends and turns Always insulate the entire suction line Both lines should be insulated when routed through an attic or when routed through an underground raceway When routing r...

Страница 6: ...are plugged from the factory Outdoor units are shipped with a refrigerant charge sealed in the unit Leave the service valves closed until all other refrigerant system work is complete or the charge w...

Страница 7: ...system is free of air and water Watch the vacuum gauge as the system is pulling down The response of the gauge is an indicator of the condition of the system refer to Figure 7 With no leaks in the sy...

Страница 8: ...mum to 253 volts maximum 60 Hz single phase Outdoor units are approved for use with copper conductors only Do not use aluminum wire Refer to unit rating plate for minimum circuit ampacity and circuit...

Страница 9: ...r example a 25 foot 7 6m line set is 10 feet 3m longer than the specified 15 feet 4 6m Add 0 6 ounces 17g charge for each of the extra 10 feet 3m 10 x 0 6 6 0 ounces additional charge 3m x 17g 51g add...

Страница 10: ...42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 SEQUEN...

Страница 11: ...d stage of the thermostat is calling for more capacity a starting advantage under low voltage conditions TROUBLESHOOTING Models are factory equipped with the Comfort Alert UltraTech Diagnostics device...

Страница 12: ...for Y2 to be energized test the voltage output at the plug with a DC voltmeter The reading here should be 4 to 18 volts If NOT unplug the harness from the module and check voltage at the DC Sol pins o...

Страница 13: ...age 4 Faulty metering device Check TXV bulb installation size location and contact Check if TXV is stuck closed or defective 5 Condenser coil is dirty 6 Liquid line restriction filter drier blocked 7...

Страница 14: ...pply and the compressor S terminal 3 Compressor start winding is damaged Check compressor motor winding resistance Yellow ALERT Flash Code 7 Open Run Circuit Current only in start circuit 1 Open circu...

Страница 15: ...HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Отзывы: