Sump Depths: 

16

’ 0” – 30’ 0” – 1 Guide rail brace required 

30-

‘0” – 45’0” – 2 Guide rail braces required 

 

7.  Exterior Piping; 

Install the inlet hub(s) in the side of basin and install inlet piping in the hub and grout, or install inlet pipe(s) 
directly into basin and grout. Install drain pipe form valve box (if required) to basin. Slope pipe to give proper 
drainage to basin. Install vent piping in side of basin (if required). Extend piping to a proper elevation above 
grade (as required by plans and specifications and/or local codes). All piping furnished by others. See 
Installation drawing Data for typical piping arrangement. 
 

8.  Pump and Sealing Flange: 

Assemble the Sealing Flange to the pump discharge flange using a gasket between the two.  
 

9.  Pump Installation: 

Check all piping braces and supports for proper installation and tightness. Attach one end of the lifting cable 
or chain to the pump eyebolts and the other to hook supplied on the inside of the hatch frame. 
 
Lower the pump into the basin locating rail guide between the two guide rails. Attach the upper end of lifting 
assembly to a hook provided on the inside of hatch frame.  
 

10.  Float Switches 

Mount the float switch mounting bracket to the door and frame assembly using 3/8

–16UNC stainless steel 

screws. Include a dielectric gasket

 

(by others) between dissimilar metals to avoid galvanic corrosion. Allow 

excess float cable to loop over mounting bracket. The sump level is controlled by Keen Pump float switch 
controls. The float is held in position in the sump by a weight attached to the power cord above the float. The 
cord supports the float and is adjusted for height from the surface. Duplex systems use three controls: one at 
both pumps off, one set at one pump on, and one set for both pumps on. Pumps alternate operation on each 
successive cycle with a Keen Pump Panel. The alarm level is usually set above the override level as it is 
possible for one pump to fail and the other to operate on the override level with the sump level never reaching 
the alarm level. Do not let floats rest against basin wall or bottom, or entangle with each other or pump(s). 
 

11.  Panel Mounted Remote from Basin: 
 

If the Control Panel is remotely located, install conduit coupling through basin wall.  Screw protective bushing 
from inside basin into coupling (all furnished by others), Make connections outside station using wiring, 
conduit seals (potted) and conduit to remotely located  Panel (conduit and seals not furnished). Insert the 
power and sensor cords through the coupling provided with the bushing. Grout in coupling goes through sump 
wall (by others). When installing pump power cords, make certain that cords do not rub against pump or on 
bottom of basin. Shorten cords to suit the installation.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание KL

Страница 1: ...07 8031 _______________________________________________________________________________ INSTALLATION AND SERVICE INSTRUCTIONS FOR KL GUIDE RAIL SYSTEM SUBMERSIBLE NON CLOG SEWAGE PUMPS _______________...

Страница 2: ...anual before operating pump Most accidents can be avoided by using COMMON SENSE KEEN PUMP is not responsible for losses injury or death resulting from a failure to observe these safety precautions mis...

Страница 3: ...There is no need to disconnect any piping or electrical connections to remove a pump for inspection or routine maintenance checks A typical system will operate on float control switches A bottom floa...

Страница 4: ...e box or main piping Install horizontal run extending through the wall of basin Secure vertical run to the vertical discharge piping using the appropriate method i e flange weld gasketed collar coupli...

Страница 5: ...ielectric gasket by others between dissimilar metals to avoid galvanic corrosion Allow excess float cable to loop over mounting bracket The sump level is controlled by Keen Pump float switch controls...

Страница 6: ...n by means of the chain or cable Disconnect the flexible conduit power and sensor cords from the control panel Pull the pump cord down through the pipe coupling while holding the cord on the underside...

Страница 7: ...ar the plugging 6 Discharge head may be too high Check elevation against design point of pump 7 Improper discharge flow Check for correct impeller size and proper voltage 8 Check for possible broken o...

Страница 8: ...using a phase converter or if 3 phase power is supplied by only two transformers making an open Delta system WARRANTY EXCLUSIONS Keen Pump specifically disclaims the implied warranties of merchantabil...