E10
Maintenance
V1.00
25
© KEBA 2023
Error
Possible causes
Remedy
The status LED
lights up red
continuously.
An error has occurred.
●
Restart the KC-E10 (see
●
Contact a service technician or
installation engineer.
The network
LED does not
light up or the
device is not
found in the net-
work.
The network cable is not connected
correctly to the network connection.
●
Ensure that the network cable
is connected correctly to the
network connection.
The KC-E10 is not in the same lo-
cal network.
●
Connect the KC-E10 with the
same router/switch.
The device sup-
plies unrealistic
measured val-
ues.
Incorrect connections or faulty con-
figuration
●
Connection of voltages from
L1, L2, L3, N.
●
Assignment of current trans-
formers to the phases: CT L1
also measures current of
phase L1?
●
Current transformer connected
in correct direction (see
●
Check whether the current
transformers are configured
correctly via Modbus.
Critical system errors and warnings are saved in internal non-volatile mem-
ory for service purposes and can be read out by KEBA.