CP.08
DC current
–
–
ru.15
Resolution
Meaning
0.1 A
Display of the calculated DC output current in ampere.
No.
Name
r/w Enter
Origin
CP.09
DC voltage
–
–
ru.19
Resolution
Meaning
1 V
Display of actual DC link voltage in volt. The value is measured at the
DC output terminals of the COMBIVERT R6-S.
No.
Name
r/w Enter
Origin
CP.10
peak DC voltage
–
–
ru.20
Value range
Meaning
0…1000 V
Parameter CP.10 enables to recognize voltage peaks within an operat
-
ing cycle. For that the highest value of CP.09 is stored in CP.10. The
peak value memory can be cleared by pressing the UP and DOWN
key or over bus by writing any value you like to the address of CP.10.
Switching off COMBIVERT R6-S also clears the memory.
No.
Name
r/w Enter
Origin
CP.11
power module temperature
–
–
ru.38
Resolution
Meaning
1 °C
Display of the actual power module temperature. On exceeding the
maximum power module temperature (see "technical data") the modu
-
lation is switched off and error E.OH is displayed. Message E.nOH is
displayed after the cooling period. The error can be reset now.
No.
Name
r/w Enter
Origin
CP.12
OL counter display
–
–
ru.39
Resolution
Meaning
1 %
The permanent load of the COMBIVERT R6-S can be evaluated with
this parameter, in order to avoid an E.OL error (in-time load reduction).
Error E.OL is released, if the overload counter reaches 100 %.