4. Installation
4. Installation
4.1
EMC-compatible control cabinet installation
1
Mains fuse
150 mm
30 mm
150 mm
1
2
8
10b
9b
10a
10c
11
11a
12
4
3
5
150 mm
150 mm
6
7
9a
Control circuit
Power circuit
Direction of the
cooling fins
2
Main contactor
3
EMC side-mounted filter
(≥ size 25 R-S or R6-N)
EMC sub-mounted filter
(≤ size 19 R6-S)
4
If necessary, external voltage limi-
tation / synchronisation
5
Commutation choke / harmonic
filter
6
COMBIVERT R6
7
if necessary external DC fuses
8
Frequency inverter
9a
DC lines with ferrite
9b
Motor line with ferrite
10
A
Protective Earth (PE) on the
mounting plate control circuit
10b
Protective Earth (PE) on the
mounting plate power circuit
10c Equipotential bonding with the
housing earth
11
Mains connection power circuit
11 A Mains connection control circuit
12
Control lines
Large area contact at the mounting
plate
Figure 9:
EMC-compatible control cabinet installation
4.2
Installation instructions
•
Install and ground the R6 on a stationary system.
•
Mist, water, or other liquids and vapors must not be allowed to permeate the device.
•
Allow for sufficient heat dissipation if installed in a dust-proof housing.
•
When operating the COMBIVERT in an explosion proof environment, install the unit in an
appropriate enclosure in accordance with the local regulations and codes.
•
Protect COMBIVERT against conductive and aggressive gases and liquids.
•
For EMC reasons, the lines between R6 and commutation reactor/harmonic filter must be lim
-
ited to < 1m or shielding must be carried out.
•
The frequency inverters must be placed in the immediate vicinity of the R6-S.