22
CP-Parameter for open-loop operation
CP34 comparison level 2
Co-domain
Setting Description
-30000,00…30000,00
4,00
This parameter determines the switching level for relay
output 1. After the switching of the relay, the value can
move within a window (hysteresis), without the relay
dropping off.
Output variable
Hysteresis
Frequency 0.5 Hz
DC link voltage 1 V
Analog setpoint 0,5 %
Active current 0.5 A
Temperature 1 °C
CP35 AN1 interface selection
The setpoint input (AN1) of the control can be triggered with different signal levels. In order to
correctly evaluate the signal, this parameter must be adapted to the signal source.
Value Set value signal
0
0…±10 V dc / Ri = 55 kΩ
1
0…±20 mA DC / Ri = 250 Ω
2
4…20 mA DC / Ri = 250 Ω
CP36 select 50Hz/60Hz mode
When units or machines are delivered in the area of application of UL an adaption of the
factory setting to the valid operating data there can be done with this parameter. The control
release must be opened for the changeover, since otherwise error "Operation not possible"
appears.
Value Default value
0
Current values and limits, motor data, frequencies and speed relate to a 50 Hz
mains with 400 V rated voltage.
1
Current values and limits, motor data, frequencies and speed relate to a 60 Hz
mains with 480 V rated voltage.
CP37 warning dOH stop. mode (only for devices with temperature input)
This parameter determines the response of the drive to the external temperature monitor-
ing.
The function is switched off at factory setting.
The power circuit terminals T1/T2
must be connected to activate the function. Then the response can be adjusted according to
the following table. If the overtemperature condition is past, the message „No ERROR drive
overheat" (or no ABN.STOP drive overheat") is output. Only then the error can be reset or the
automatic restart can be carried out.