Relay output 1
Relay output 2
Special Adjustments
CP.31 and CP.32 determine the function of the two outputs.
CP.31 for relay output 1 (terminal X2A.24...X2A.26)
CP.32 for relay output 2 (terminal X2A.27...X2A.29)
The switching level of CP.32 is CP.33!
Value Function
0
No function
1
On; active when unit has voltage applied to it
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (no auto-reset)
6
Warning or error message at abnormal stopping
7
Overload alert signal
8
Overtemperature alert signal power modules
9
External Overtemperature alert signal motor
10
Motor thermal relay tripped (OH2)
11
Overtemperature alert signal interior (OHI)
12
Cable breakage on analog input 1 (4...20 mA)
13
Cable breakage on analog input 2 (4...20 mA) {F5G only}
14
Max. constant current (stall, CP.25) exceeded
15
Max. ramp current (LA-Stop CP.24) exceeded
16
DC-braking active
17
Power off
18
Motor brake control
19
PID control difference > switching level {F5G only}
20
Actual value= set value (CP.3= Fcon, rcon; not at noP, LS
error,SSF)
21
Accelerate (CP.3 = FAcc, rAcc, LAS)
22
Decelerate (CP.3 = FdEc, rdEc, LdS)
23
Real direction of rotation = set direction of rotation
24
Actual load utilization (CP.6) > 100%
25
Active current > switching level
26
Actual DC voltage (CP.7)>switching level
27
Actual frequency (CP.1) > switching level
28
Set frequency (CP.2) > switching level
29
Ref. point run complete {F5G only}
30
Actual torque > level {F5G only}
31
Absolute speed on AN1 > switching level
32
Absolute speed on AN2 > switching level {F5G only}
33
Absolute. speed on AN3 > switching level {F5G only}
34
Set value on AN1 > switching level
35
Set value on AN2 > switching level {F5G only}