31
Special Adjustments
Analog output 1
Analog output 1
Amplification
10V
CP.30
100%
-100%
100%
-100%
in
out
Adjustment example :
The analog output shall give +10 V at 70
Hz instead of at 100 Hz: CP.30 = 1.43
100 Hz
CP.30 = -––––– = 1.43
70 Hz
With the amplification (gain), the output voltage of the analog output can
be tuned with respect to the signal. An amplification of 1 corresponds to
±100 % = ±10 V.
Adjustment range:
0...20
Resolution:
1
Factory setting:
2
Note:
Enter-Parameter
Adjustment range:
-20.00...20.00
Resolution:
0.01
Factory setting:
1.00
CP.29 defines the function of analog output 1.
Value Function
0
Absolute actual frequency (CP.1)
100Hz= 100%
1
Absolute set frequency (CP.2)
100Hz= 100%
2
Actual frequency (CP.1)
±100Hz= 100%
3
Set frequency (CP.2)
±100Hz= 100%
4
Output voltage (CP.9)
500V= 100%
5
Actual DC voltage (CP.7)
1000V= 100%
6
Phase current (CP.4)
2 x rated current= 100%
7
Active current
± 2 x rated current= 100%
8
Digital
±100Hz= 100%
9
External PID output
±100Hz= 100%
10
Absolute external PID output
100Hz= 100%
11
Absolute active current
2 x rated current= 100%
12
Power module temperature
100 °C= 100%
13
Motor temperature {F5G}
150 °C= 100%
14
Reserved{F5M}
15
Reserved{F5M}
16
Reserved{F5M}
17
Reserved{F5M}
18
Reserved{F5M}
19
Reference frequency {F5G}
±140Hz= 100%
20
Absolute reference frequency {F5G}
140Hz= 100%