36
INSTALLATION AND cONNEcTION
4.3 Overtemperature shutdown
In order to protect the system against overtemperatures, the chokes from size 25 are
equipped with temperature switches. This must be connected with the input terminals
T1/T2 of the drive converter.
4.3.1 Rated data Nc contact temperature monitoring
contact
Data
Tripping temperature
155 °C
AC cos φ = 1.0
2.5 A / 250 V
AC cos φ = 0.6
1.6 A / 250 V
DC ohmic
1.6 A / 24 V
DC ohmic
1.25 A / 48 V
Table 11:
Rated data NC contact
Содержание COMBILINE Z2 Series
Страница 2: ......
Страница 52: ...52 NOTIZEN...