Technical data | 4
ma_dr_e6-hf-filter-nb-20337731_en
15
The following table shows the maximum fuse size of the type
/
1:1 dimensioning and an input voltage of 480 V. In case of other dimension-
ing, the values must be designed for the current and the
downstream drive controller. The marks approved for UL are depending on
the connected drive controller and are described there accordingly.
SCCR 30kA
SCCR 100kA
12E6T60-3000
in Vorbereitung
in Vorbereitung
Tab. 3:
Fuse protection according to UL type gR / aR
4.2.4 Interference suppression level
To comply with the required limit class the specified motor cable length must not be ex-
ceeded, depending on the switching frequency.
Filter
33E6T60-3150
Interference voltage (limit class
C2 (C3)
Rated switching frequency
2 kHz
4 kHz
8 kHz
Maximum motor cable length (low-capacity)
100 m
50 m (100 m)
100 m
Tab. 4:
Interference suppression level 33E6T60-3150
4.2.5 Insertion loss
Measurement results of the insertion loss in accordance with
f / MHz
Attenuation / dB
a
b
c
d
Fig. 2:
33E6T60-3150_attenuation
a Asymmetrical insertion loss (Common Mode)
b Unsymmetrical insertion loss (Differential Mode)
c Symmetrical insertion loss (0.1Ω/100Ω system)
d Symmetrical insertion loss (100Ω/0.1Ω system)