4 | Technical data
KEB Automation KG
14
ma_dr_e6-hf-filter-nb-20337731_en
4.1.4 Electrical operating conditions
4.1.4.1 Device classification
Requirement
Standard
Class
Notes
Overvoltage category
III
-
Pollution degree
2
Non-conductive pollution, occasional condensa-
tion when
is out of operation.
4.2 Electrical data
12E6T60-3000
Rated input voltage
400 V
Rated input voltage (UL)
480 V
Input voltage range
0…528 V
Peak input voltage
550 V für max. 1 min/h
Mains phases
3
Mains frequency
50/60 Hz ±2 Hz
Mains form
TN, TT, IT
Leakage current according to EN 60939-1:
2010 (Annex A9)
0,8 mA @ 400 V; 1,0 mA @ 480 V
Rated input current
840 A
Rated input current (UL)
744 A
Overload (60s)
150 %
Power dissipation
110 W
Construction and protection class
IP00
Suitable KEB housing size
F6 / 9
4.2.1 Fuse protection according to
The following table shows the maximum fuse size of the
with a 1:1 dimensioning
and an input voltage of 400 V. In case of other dimensioning, the values must be de-
signed for the current and the
rating of the downstream drive controller.
SCCR 30kA
SCCR 100kA
12E6T60-3000
-
2 x 450 A
Tab. 1:
Fuse protection according to
4.2.2 Fuse protection according to UL Class J
The following table shows the maximum fuse size of the type
with a
1:1 dimensioning and an input voltage of 480 V. In case of other dimension-
ing, the values must be designed for the current and the
rating of the
downstream drive controller.
SCCR 5kA
SCCR 10kA
SCCR 18kA
12E6T60-3000
in Vorbereitung
in Vorbereitung
in Vorbereitung
Tab. 2:
Fuse protection according to UL Class J
4.2.3 Fuse protection according to UL type gR / aR