8

8

9

Defrost (Heater) Relay

  Strip the end of the 2 wires used for the defrost control.

  Locate (2) 90° female spade connectors in the accessories kit.

  Crimp on the female connectors.

  Plug the connectors to the COM and NO positions of the Defrost 

Relay. 

Defrost (Heater) Relay Using the KE2 Wire Harness

  The orange wires are used for the heater control.

  Locate the orange with black stripe, and black with orange stripe.

  Plug the black with orange stripe to the COM terminal.

  Plug the orange w. black stripe to the NO position of Defrost Relay.

Confirm combined heater load is not over 30 amps.

9

10

Liquid Line Solenoid /Compressor Relay

  Strip the end of the 2 wires used for the liquid line solenoid. 

  Locate 2  90° female spade connectors in the accessories kit.

  Crimp on the female connectors.

  Plug the connectors to the COM and NO positions of the Liquid  

Line Solenoid /Compressor Relay

Liquid Line Solenoid (LLS)/Comp. Relay Using KE2 Wire Harness

  The yellow wires are used for Liquid Line Solenoid control.

  Locate a 3-position connector from the accessories kit.

  Fasten the black with yellow stripe to the fused lead.

  Fasten yellow w. black stripe from the LLS to NO terminal position.

  Plug into the location as indicated in Wiring Schematic.

Confirm compressor load is not over 30 FLA.

Fan Relay

  Strip the end of the 2 wires used for fan control.

  Locate 2  90° female spade connectors in the accessories kit.

  Crimp on the female spade connectors. 

  Plug the connectors to the COM and NO positions of the Fan Relay. 

Fan Relay Using the KE2 Wire Harness

  The blue wires are used for fan control.

  They are blue with a black stripe, and the black with a blue stripe.

  Plug the black with a blue stripe to the COM terminal. 

  Plug the blue with a black stripe to the NO position of the Fan 

Relay

Confirm combined  fan motor load is not over 30 FLA.

10

KE2 Adaptive

Control

Quick Start Guide

Содержание AdaptiveControl

Страница 1: ...rovided Conduit to go between the controller and the evaporator 2 Conduit connectors straight or elbow as required 8 High voltage wires matched to the load of the heaters fans liquid line solenoid and...

Страница 2: ...Vapor Mix Restrictor TEV or EEV Warm Liquid ColdVapor HotVapor Warm Air Cold Air Evaporator Compressor Condenser SaturationTemp F from receiver pressure LiquidTemp atValve F Subcooling Suction Pressu...

Страница 3: ...lect two places that are the last to defrost preferably at each end of the evaporator More often than not on coils the location of the sensor is a short distance from the end approximately 1 to 1 1 2...

Страница 4: ...e Control Cutalengthofconduittogofromthecontrollertotheevaporator Measure the distance between the controller and evaporator to account for the extra length necessary to properly route conduit Determi...

Страница 5: ...end of the conduit to the controller 5 5 115V 208 240V Wiring the controller Locate the Voltage Selector Switch It is a 2 position switch with red indicator The selected voltage will be displayed on...

Страница 6: ...lug the connectors to the COM and NO positions of the Liquid Line Solenoid Compressor Relay Liquid Line Solenoid LLS Comp Relay Using KE2 Wire Harness The yellow wires are used for Liquid Line Solenoi...

Страница 7: ...he controller to the plastic posts Connecting sensor wires to controller The temperature sensors are designed to be attached to the con troller using 2 position screw terminals The terminals are locat...

Страница 8: ...controller 15 Evaporator wiring Fans Strip the ends of the wires con nected to the KE2 Adaptive Control used to control the evapo rator fans The fan wires from the controller can be attached to the te...

Страница 9: ...ect L2 Neutral to the remain ing defrost leads The defrost safety should not be re moved from the circuit Its purpose is to prevent the heaters from over heating and causing damage 18 Copyright 2016 K...

Страница 10: ...ary 2016 Page 10 Copyright 2016 KE2 Therm Solutions Inc Washington Missouri 63090 Figure 8 Wiring Schematic Ladder Diagram Figure 8 Wiring Schematic Using KE2Terminal Board KE2 AdaptiveControl Quick S...

Страница 11: ...ew included The end with multiple loops is designed to hold the sensor Locate the best place to install the sensor The sensor should be located between 6 and 12 inches away from the face of the evapor...

Страница 12: ...erference being introduced into the sensor wires Interference can be introduced when sensor wires are located near high voltage lines High voltage is defined by Underwriter s Laboratories as above 30V...

Страница 13: ...venient loca tion where it can be easily located for future service 27 Setting the dip switch to activate on board buzzer To disable the audible alarm buzzer feature of the KE2 Adaptive Control the di...

Страница 14: ...d dFt diF OFFt Runt FrEF AU1 StA1 AU2 StA2 tS2 tOd d1 d2 d3 d4 d5 d6 d7 d8 d9 d10 d11 d12 dtSP drnt fdSP Fndt FndF Pdt HAO LAO tAd Adr Unt CLAL Schedule Defrost w Custom Defrost Per Day tS dtyP dFit d...

Страница 15: ...0V 208 240V StorageTemp 40 to 120 F 40 to 49 C OperatingTemp 40 to 120 F 40 to 49 C Display 4 digit 7 segment LED IP Rating IP65 Inputs 4 3 colored 15 temp sensors KE2 SKU 21151 2 dual purpose tempera...

Страница 16: ...ive cycles ECdF Excessive Defrost Controller has performed 11 consecutive defrost cycles without terminating on temperature PF Power Failure Indicates power has been off and just turned on only when d...

Страница 17: ...00 diS 23 59 diS d2 Start time of Defrost 2 0 00 diS 23 59 diS d3 Start time of Defrost 3 0 00 diS 23 59 diS d4 Start time of Defrost 4 0 00 diS 23 59 diS d5 Start time of Defrost 5 0 00 diS 23 59 diS...

Страница 18: ...lock d12 Defrost 12 Setpoint Start time of Defrost 12 when in defrosts per day dPd is custom CUSt based on 24 hour clock dAUt Defrost Auto Variable Defrost is in Automatic mode i e normal operation dE...

Страница 19: ...arm Offset LAO for the amount of time in theTempera ture Alarm Delay tAd NOAL No Alarm Alarm System is clear of alarms OFF System Off System State The system is currently not running OFFt Minimum Comp...

Страница 20: ...ay then press Use the up arrow and down ar row to set the time STEP 7 Press the button to save settings and return to the main screen room temp will be displayed Custom Defrost Setup The following ste...

Отзывы: