background image

© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.1.35 January 2016

Page 2

KE2 Adaptive

Control

Quick Start Guide

for low temperature applications, and 8-10 degrees for medium 

temperature.

Subcooling - There should be a solid column of liquid at the inlet of 

the valve.  This can be verified by looking at the sight glass, however, 

the proper method requires measuring the subcooling of the liquid 

entering the valve.

Verify Temperature Difference

A typical Temperature Difference (TD) between the coil temperature 

and the air temperature is between 5 and 15°F.   An insufficient TD, 

between the coil and air temperature, indicates a system issue that 

needs to be addressed before installing the KE2 Adaptive Control.

Understanding Frost

The air exiting side of the evaporator is often the coldest spot on 

the coil. As air travels through the fins of the evaporator, the Relative 

Humidity will reach 100%. Moisture will begin to drop out of the air 

and deposit on the coil surfaces to form frost. Although frost typi-

cally has a negative connotation when discussed in refrigeration, 

initial frost formation has a positive effect. Some may even say “frost 

is our friend.” It is not uncommon to see a small amount of frost on 

the coils that have KE2 Adaptive Control controllers installed. The KE2 

Adaptive Control is continually measuring, monitoring, and manag-

ing the frost to assist in maximum energy efficiency. When the ef-

ficiency of the coil is reduced due to excessive frost, the KE2 Adaptive 

Control will initiate a defrost.

Liquid/Vapor Mix

Restrictor,

TEV or EEV

Warm Liquid

Cold Vapor

Hot Vapor

Warm Air

Cold Air

Evaporator

Compressor

Condenser

Saturation Temp 

 

 °F 

(from receiver pressure)
  

Liquid Temp at Valve   

 °F

Subcooling   °

Suction Pressure 

 

  PSI 

Suction Temp 

 

   °F

(evaporator outlet)

  

Saturation Temp 

 

   °F 

(calculated from Suct. Pressure)

Superheat  

°       

Temp Difference (TD)  

 °F 

(return air minus coil temp)

Coldest point in evap  

 °F

AMPS  

  

Trouble Shooting Diagram

Discharge Pressure   

  PSI

Refrigerant 

Arriving at the Jobsite

When arriving at any jobsite, it is good practice to verify the correct 

operation of the system. Even systems running for a considerable 

amount of time without requiring a service call may not be running 

properly.  

Inspect the coil to see the current frost pattern.  If the unit has not 

recently performed a defrost, look for the heaviest area of frost.  This 

will be used to locate the coil sensor.

Installers should account for a full system diagnostic in the installa-

tion estimate for the controller.  

Although it may seem unnecessary, identifying system issues before 

the controller is installed will save time overall.  It will also allow the 

controller to provide the highest energy savings.

Verify the system is running correctly.  Taking several measurements 

will help determine the current health of the system. Using the dia-

gram below, fill in the necessary information.

Two of the most critical indicators of system health are the super-

heat and subcooling.

Superheat - Superheat is the most overlooked inefficiency in exist-

ing systems.  Typically the superheat on a TEV is set when there is not 

product in the controlled space, if it is set at all.

When applying the controller to an existing system with a mechani-

cal expansion valve, the superheat should be between 6-8 degrees 

Содержание AdaptiveControl

Страница 1: ...rovided Conduit to go between the controller and the evaporator 2 Conduit connectors straight or elbow as required 8 High voltage wires matched to the load of the heaters fans liquid line solenoid and...

Страница 2: ...Vapor Mix Restrictor TEV or EEV Warm Liquid ColdVapor HotVapor Warm Air Cold Air Evaporator Compressor Condenser SaturationTemp F from receiver pressure LiquidTemp atValve F Subcooling Suction Pressu...

Страница 3: ...lect two places that are the last to defrost preferably at each end of the evaporator More often than not on coils the location of the sensor is a short distance from the end approximately 1 to 1 1 2...

Страница 4: ...e Control Cutalengthofconduittogofromthecontrollertotheevaporator Measure the distance between the controller and evaporator to account for the extra length necessary to properly route conduit Determi...

Страница 5: ...end of the conduit to the controller 5 5 115V 208 240V Wiring the controller Locate the Voltage Selector Switch It is a 2 position switch with red indicator The selected voltage will be displayed on...

Страница 6: ...lug the connectors to the COM and NO positions of the Liquid Line Solenoid Compressor Relay Liquid Line Solenoid LLS Comp Relay Using KE2 Wire Harness The yellow wires are used for Liquid Line Solenoi...

Страница 7: ...he controller to the plastic posts Connecting sensor wires to controller The temperature sensors are designed to be attached to the con troller using 2 position screw terminals The terminals are locat...

Страница 8: ...controller 15 Evaporator wiring Fans Strip the ends of the wires con nected to the KE2 Adaptive Control used to control the evapo rator fans The fan wires from the controller can be attached to the te...

Страница 9: ...ect L2 Neutral to the remain ing defrost leads The defrost safety should not be re moved from the circuit Its purpose is to prevent the heaters from over heating and causing damage 18 Copyright 2016 K...

Страница 10: ...ary 2016 Page 10 Copyright 2016 KE2 Therm Solutions Inc Washington Missouri 63090 Figure 8 Wiring Schematic Ladder Diagram Figure 8 Wiring Schematic Using KE2Terminal Board KE2 AdaptiveControl Quick S...

Страница 11: ...ew included The end with multiple loops is designed to hold the sensor Locate the best place to install the sensor The sensor should be located between 6 and 12 inches away from the face of the evapor...

Страница 12: ...erference being introduced into the sensor wires Interference can be introduced when sensor wires are located near high voltage lines High voltage is defined by Underwriter s Laboratories as above 30V...

Страница 13: ...venient loca tion where it can be easily located for future service 27 Setting the dip switch to activate on board buzzer To disable the audible alarm buzzer feature of the KE2 Adaptive Control the di...

Страница 14: ...d dFt diF OFFt Runt FrEF AU1 StA1 AU2 StA2 tS2 tOd d1 d2 d3 d4 d5 d6 d7 d8 d9 d10 d11 d12 dtSP drnt fdSP Fndt FndF Pdt HAO LAO tAd Adr Unt CLAL Schedule Defrost w Custom Defrost Per Day tS dtyP dFit d...

Страница 15: ...0V 208 240V StorageTemp 40 to 120 F 40 to 49 C OperatingTemp 40 to 120 F 40 to 49 C Display 4 digit 7 segment LED IP Rating IP65 Inputs 4 3 colored 15 temp sensors KE2 SKU 21151 2 dual purpose tempera...

Страница 16: ...ive cycles ECdF Excessive Defrost Controller has performed 11 consecutive defrost cycles without terminating on temperature PF Power Failure Indicates power has been off and just turned on only when d...

Страница 17: ...00 diS 23 59 diS d2 Start time of Defrost 2 0 00 diS 23 59 diS d3 Start time of Defrost 3 0 00 diS 23 59 diS d4 Start time of Defrost 4 0 00 diS 23 59 diS d5 Start time of Defrost 5 0 00 diS 23 59 diS...

Страница 18: ...lock d12 Defrost 12 Setpoint Start time of Defrost 12 when in defrosts per day dPd is custom CUSt based on 24 hour clock dAUt Defrost Auto Variable Defrost is in Automatic mode i e normal operation dE...

Страница 19: ...arm Offset LAO for the amount of time in theTempera ture Alarm Delay tAd NOAL No Alarm Alarm System is clear of alarms OFF System Off System State The system is currently not running OFFt Minimum Comp...

Страница 20: ...ay then press Use the up arrow and down ar row to set the time STEP 7 Press the button to save settings and return to the main screen room temp will be displayed Custom Defrost Setup The following ste...

Отзывы: