background image

Copyright 2011 KE2 Therm Solutions, Washington, Missouri 63090

therm

solutions

TM

Installation N.1.1 August 2011

Page 3

KE2 

Evaporator

Efficiency 

Installation Instructions

for easy viewing of the room temperature and/or system status.  

See 

Figure 1 

for locations.

If installing the controller on the face of the evaporator, preexist-

ing knockouts on the evaporator should be used for installing 

the high voltage wiring.  If knockouts do not preexist, hole(s) 

may be carefully cut into an unobstructed area of the evapora-

tor case.  If modifying the face of the evaporator is not feasible 

or desired, the controller’s conduit knockouts may be used with 

½ inch conduit.

The bottom side of the controller includes a cutout with cable 

tie slots providing a strain relief for the low voltage and sensor 

wires.  Additional knockouts are available on either side if con-

duit is preferred. 

Installation & Wiring

The KE2 Evap is supplied with pluggable connectors for all 

connections. Pluggable connectors permit the controller to 

be placed in a safe location while the wiring is installed. They 

also simplify the wiring, allowing the wires to be fastened to the 

screw terminals in the open air.  Once all wiring is completed 

using accepted wiring practices, it is plugged into the controller 

prior to final mounting.  

Although there is one pressure transducer and four temperature 

sensor inputs, when used with mechanical valves (TEVs), KE2 

Evap only requires the 

(2) sensors supplied with the kit .  

One 

sensor reads the return air temperature and the other measures 

the coil temperature. 

NOTE! Sensor location is critical to the 

proper operation of the controller .  

Return Air Temperature Sensor - 

The air temperature sensor is 

installed in the return air of the evaporator using the included 

sensor mount.  Most applications allow the sensor mount to 

be installed using an existing screw.  On evaporators where us-

ing an existing screw is not possible, the included self-tapping 

screw may be used to secure the sensor mount to the evapora-

tor. 

 Note: Be careful to avoid damage to an evaporator tube 

or causing a leak in the drip pan .  

When installing, it is impor-

tant to prevent the air sensor from coming into contact with the 

mounting bracket, cable ties, or any other solid material.  

Figure 

shows an example of how to mount the sensor.  The sensor 

must be a minimum of 6 inches from the coil surface.

Location

The KE2 Evap was developed with ease of installation in mind.  

The controller is supplied in an enclosure, and encapsulated to 

protect the circuitry from moisture damage.  This extra level of 

protection allows the controller to be installed in the refriger-

ated space.  

When installing the controller, it may either be installed on an 

interior/exterior wall or on the evaporator.  Many evaporators 

have sufficient space to install the controller on the face of 

evaporator or on its housing.  Locating the controller as close to 

the evaporator as possible reduces the amount of wiring when 

converting existing systems, as well as when it is applied on new 

applications.  

Users may find it beneficial to install the controller in a loca-

tion providing easy access -- on the wall or near the entrance.  

This enables the user to easily view the display, and eliminates 

the need to use a ladder or lift to modify the setpoints or check 

alarms.  

If viewing the temperature outside the walk-in or refrigerated 

room is desirable, the KE2 Evap may be used as a digital thermo-

stat.  The controller is then installed near the door of the space 

KE2 

Evaporator

Efficiency

TM

therm

solutions

ENTER

BACK

2

2

KE2 

Evaporator

Efficiency

TM

therm

solutions

ENTER

BACK

2

2

KE2 

Evaporator

Efficiency

TM

therm

solutions

ENTER

BACK

2

2

On the wall

On the evaporator

At the entrance

Figure 1 - KE2 Evap Installation Locations 

Air 

Sensor

>6”

Return Air

Figure 2 - Return Air Sensor Placement

Содержание Evaporator Efficiency

Страница 1: ...erm Solutions Providing Advanced Energy Saving Technology for Commercial Refrigeration and AC Systems KE2 EvaporatorEfficiency Installation Instructions Installation N 1 1 August 2011 KE2 EvaporatorEf...

Страница 2: ...rameters Page 12 Table 3 Controller Menus and Menu Parameters Pgs 13 15 Variables Menu Page 13 Alarm Status Menu Page 13 Manual Menu Page 13 Setpoint Menu Page 14 15 Table 4 Defrost Defaults Page 15 C...

Страница 3: ...mount to be installed using an existing screw On evaporators where us ing an existing screw is not possible the included self tapping screw may be used to secure the sensor mount to the evapora tor No...

Страница 4: ...proximately half the distance between the heaters if possible Figure 4 shows the proper sensor placement Due to the many factors influencing the evaporator perfor mance it is impossible for KE2Therm t...

Страница 5: ...ining leg L2 should be connected to one lead on the solenoid com pressor contactor The remaining lead should be connected to the normally open NO position on the terminal Alarm Relay The alarm relay i...

Страница 6: ...NC NO NO NC NO NC COM COM NC Power In green red black NO Transformer 3A Relay 3A Relay COM COM COM NC NO COM NC NO 18V DI 1 DI 3 DI 2 ElectricValve Temperature Sensors 4 PressureTransducer RJ45 Ether...

Страница 7: ...BACK Condenser KE2 Evap Compressor Evaporator Defrost SolenoidValve EPR with Suction Stop CheckValve CheckValve HSV ElectricValve Liquid Line Solenoid Compressor Relay Liquid Line SolenoidValve Defro...

Страница 8: ...matic Controller New Install Legend EFM Evaporator Fan Motor DH Defrost Header LLS Liquid Line Solenoid AL Alarm PT PressureTransducer TSUCTION SuctionTemperature TAIR Return AirTemperature TCOIL Evap...

Страница 9: ...Max Current Ratings Amps are Total All Heaters Relay Box P N 230V 3O 460V 3O 575V 3O 20217 54 Amps 52 Amps 52 Amps 20218 68 Amps 65 Amps 62 Amps 20219 80 Amps 77 Amps 62 Amps L egend EFM Evaporator Fa...

Страница 10: ...ermsolutions TM Installation N 1 1 August 2011 Page 10 R 0 210 R 0 105 11 75 9 0 0 5 2 2 PressureTransducer 0 75 6 75 1 40 2 03 0 67 0 95 5 75 2 03 6 5 female 1 4 SAE with depressor Temperature Sensor...

Страница 11: ...e controller is designed to work with electric hot gas and off time defrosts The last set point is the valve type The controller is defaulted to be used with a mechanical valve but may be used with a...

Страница 12: ...es To move through controller menus To return to Main Menu Indicator lights Red light critical alarm system off Yellow light non critical alarm system running Green light compressor on Green flashing...

Страница 13: ...n Adjustable view only Alarm Status Parameters Abbrev Description Pressure Sensor Alarm PRSA Suction pressure sensor is shorted or open Suction Temp Sensor Alarm STSA Suction temperature sensor is sho...

Страница 14: ...rm Offset HITA The air temperature rises above the setpoint of the Room Air Setpoint plus the high temperature alarm offset High Temperature Alarm Delay HITD If air temperature rises above the setpoin...

Страница 15: ...F 10 degrees F 0 to 120 minutes 60 minutes 0 to 20 degrees F 4 degrees F 0 to 30 minutes 10 minutes DOOR 2ND Setpoint SPT2 OFF SOFF XTA1 DOOR Open Close Close DOOR 2ND Setpoint SPT2 OFF SOFF XTA2 OFF...

Страница 16: ...so special software is not required A standard Ethernet cable should be used between the periph eral device and the controller One end is connected to the controller and the other to the Ethernet por...

Отзывы: