Work in accordance with the electric local wiring rules and standards and the working standard specified by the power company.
In order to avoid motor burn-out due to over current, be sure to mount an overload protection device (such as the motor 
breaker) that matches the ratings on each fan.
(Select a motor breaker that supports the maximum current multiplied by 1.2 to 1.5 (described in the "Specifications" 
on page 8).)
Always install the earth leakage breaker. 
Connect the power cord shown as dotted lines in the "Wiring Diagram".
Open the terminal cover and pass power cord through the gum grommet.
Connect the power cord according to the "Wiring Diagram", "Power cord treatment" (on rear cover page) and "Connecting 
wiring" (on rear cover page).
When connecting the power cord, fix the power cord to the hanging 
bolt so that the power connector is not under tension. 
(The K25DSF2NET do not have terminal covers.)
As water may enter the connector along the power cord, use a trap 
or other type of treatment for the power cord (see illustration at right).  
After the power cord has been connected, always mount the terminal cover. 
(Except K25DSF2NET.)
A thermal fuse is mounted inside the motor of this product for protection. 
If the source voltage differs from ratings or if power cord is not correctly 
connected, the temperature of the motor windings may increase. In this 
case, the thermal fuse will blow and the motor will stop. Once the fuse 
blows, the motor cannot restart itself (that is, it cannot rotate). 
Locate and remove the cause of the error, and replace the motor.
Note that an unstable (or temporarily installed) power supply may cause the thermal fuse to blow and the motor may stop 
during a trial run.
After wiring, check the rotation direction in case of three phase motors.

Electric wiring cautions

Installation Instructions

In order to avoid the danger, it must be connected by qualified technician.
Incorrect wiring may result in current leakage or fire.

CAUTION

CAUTION

3.Power cord connection

This product must be properly and reliably grounded.
There is a possibility of receiving an electric shock.

CAUTION

Exercise care when you connect cords.
When operating the motor while using the different source voltage from ratings, if you 
arrange the cabling differently from that shown in the wiring diagram, or if you mistake 
single-phase for three-phase, the motor may burn out.

K25DSF2NET
K28DSM2NET
K35DSM2NET
K40DSL2NET
K40DSH2NET
K45DST2NET

Hi

Hi

N

Lo

Red

MOTOR

POWER 
SUPPLY

POWER 
SUPPLY

POWER 
SUPPLY

CAPACITOR

Wht
Blk

Hi

N

Lo

Red

MOTOR

CAPACITOR

K25DSF2NET:

There is no connecting terminal.

The tip of the unused cord must be insulated.

Wht
Blk

Lo

Hi

U
V

W

R
S

T

POWER 
SUPPLY

R
S

T

U1
V1

W1

Red

MOTOR

Wht
Blk

Brw
Yel
Blu

U
V

W

U1
V1

W1

Red

MOTOR

Wht
Blk

Brw
Yel
Blu

Lo

WIRING 

DIAGRAM

(SINGLE PHASE)

K40DTL2BET
K40DTH2BET
K45DTT2BET
K45DTH2BET

WIRING 

DIAGRAM

(THREE PHASE)

Connector (inside the terminal cover)

Terminal cover

Power cord

Trap

Power cord

Fixing 
band

(It is not supplied with K25DSF2NET.)

Hanging 
bolt

[

]

Содержание K40DSH2NET

Страница 1: ...afety Precautions on page 2 4 prior to use K35DSM2NET K40DTL2BET Table of Contents Safety Precautions 2 4 Names and Dimensions of Component 5 Maintenance and Inspection 6 Periodic Check and Maintenanc...

Страница 2: ...all components and parts If they fall it may cause an injury When combustible gas leakage occurs open the windows to make air circulate When you start the fan a spark of the electrical contacts may c...

Страница 3: ...ls or if an electricity leakage occurs in it it may cause an electric shock Stop immediately the operation in case of any abnormality noise vibration smell and request for repair May cause unexpected...

Страница 4: ...or sucking the obstacle Don t operate with the wheel to which much dust has been adhered May cause wheel breakage or motor burnout Do not install the main body and indoor air supply entrance at the pl...

Страница 5: ...350 410 480 540 B 197 206 206 218 C 22 21 5 26 25 5 D 248 298 347 395 E 400 460 525 588 F 366 426 491 554 G 350 415 480 546 H M8 M8 M8 M10 I 32 32 32 34 J 9 9 9 11 Parts name Casing A Casing B Motor...

Страница 6: ...years Inspection Criteria Indication Maintenance Remarks 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 Entire fan Update equipment 2 Casing Guide vanes 3 Wheel 5 Terminal Check noise and vibration by hearing...

Страница 7: ...f use operation time per day etc 5 Abnormal conditions from when and how it occurs 6 Handling air for general ventilation or for clean air and intended use symptom Insufficient air flow Excessive vibr...

Страница 8: ...25DSF2NET Single phase 220 240V 4 25 Hi 600 720 0 19 0 17 0 24 0 22 34 38 41 0 42 0 51 0 54 0 50 5 53 5 4 7 Lo 550 650 0 14 0 12 0 17 0 18 27 29 39 5 41 5 49 0 52 0 48 5 51 5 K28DSM2NET Single phase 2...

Страница 9: ...which requires water the place where steam generates the place where corrosive gas may generate and the place where chemicals are used Don t make a hole to the fan casing In the casing there are elec...

Страница 10: ...For power connecting removing or setting the terminal cover Install the exterior duct in over 1 100 declining slope toward outer side Make the access door opening to the side of power cord or termina...

Страница 11: ...ill stop Once the fuse blows the motor cannot restart itself that is it cannot rotate Locate and remove the cause of the error and replace the motor Note that an unstable or temporarily installed powe...

Страница 12: ...gainst the terminal cover biting power cord Power supply Fan body The tip of the power cord which is not used must be insulated Protection tapes or covers for insulation Terminal For reference only So...

Отзывы: