Installation
The
THYRO
SWITCH
can be installed horizontally or vertically. Due to the forced cooling, nearly all the warm
air produced is emitted in one direction. At maximum load, a temperature increase of max. 40°C can be expected.
If temperature-sensitive components are used, such as cable ducts, it is possible that cowls must be provided.
Distances:
Fan side:
>50mm
Heat sink outlet:
>150mm
With vertical installation it must be ensured that warm air is always emitted upwards. When installing several
THYRO
SWITCH
on top of one another, cowls should be used.