background image

THYRO

SWITCH

User Manual

Page - 2 -

Version 1.0

E

D

EBD

A0
08
0 /
 17

07-

1

 GB

2

Safety Notes

Due to the design with forced cooling, that is with the use of a fan, unimpeded air intake must in particular be
guaranteed. The cooling openings must not be covered up. The distances specified from neighboring components
must be observed. For nominal load, there is an increase in temperature between fresh air and exhaust air of max.
40°C. Temperature-sensitive components such as cable ducts should be protected by cowls. 

The 

THYRO

SWITCH

 may only be operated with a series-connected power disconnecting device. 

The 

THYRO

SWITCH

 cannot function alone as a component and must be project-planned for use with a

compensation unit. 

The 

THYRO

SWITCH

 may only be deployed in the context of its intended use. 

Even when used only as intended, a defect cannot be ruled out. In this case the currents and voltages in the load
circuit could be affected. In case of an error, the following cases are possible: Current interruption, half-wave
operation or constant energy flow. Correct design of  protective devices must therefore be ensured during project
planning.

Incorrect operation or wrong connections could lead to destruction of the device or the load.

The 

THYRO

SWITCH

 may only be connected with insulated crimping cable lugs.

Work such as assembly, maintenance and servicing may only be performed by skilled electricians. A soon as the

THYRO

SWITCH

 is connected to the power supply system, the capacitive load is charged to network peak

voltage. In addition a phase is connected directly to the load. This means that the load is under voltage, even when
switched off, and remains connected to the power supply. When working on the load, disconnection from the
network must be made under all circumstances. 

Danger to life!

Even after disconnection from the network, a residual charge remains in the capacitive load. Before working on
the equipment, it must be checked that the capacitors are isolated from the supply. The discharge time of the
capacitors must be taken into account.

Note:

 Power capacitors must be equipped with permanently connected discharge devices and be discharged

within five minutes to a residual charge of 50µC at most, or a to a voltage of 60V. If this has a disturbing effect on
the function of the electrical equipment, a warning sign must be put up in a clearly visible position stating that the
discharge time is longer than five minutes. If it is possible to come into contact with the voltage of the capacitors,
with the correct use of connectors, and these connectors can be pulled off without the use of tools, the discharge
must be complete within one minute 

(See EN 50178, Section 5.2.5)

.

For the design of the discharge equipment it must be remembered that capacitors when switched off are charged
to a direct voltage at the level of the network peak voltage.

The parallel operation of facilities with conventional protective relaying and semiconductor technology is only
possible for reactor-protected equipment. Otherwise the 

THYRO

SWITCH

 

 could be destroyed by the effects

of charge transfer.

Содержание THYRO SWITCH

Страница 1: ...HYRO SWITCH Operating Instructions Technical Parameters KBR GmbH Am Kiefernschlag 7 D 91126 Schwabach Phone 49 0 9122 6373 0 Fax 49 0 9122 6373 83 email info KBR de s s s s s ENERGIEMANAGEMENT mit System ...

Страница 2: ...ual Page I Version 1 0 EDEBDA0080 1707 1 GB Contents 1 Intentended Use 1 2 Safety Notes 2 3 Areas of Application 3 4 Installation 4 5 Connection 5 6 Commissioning 6 7 Type Overview 7 8 Declaration of Conformity 7 9 Notes 8 ...

Страница 3: ...y voltage UN Load current Power dissipation 400 500V 50Hz 60Hz max 115A 500V 70A approximately 2W per A Application area Creepage distance from control input to main circuit Rated voltage Harmonic voltage 10 5mm for SELV voltage circuits UN 10 DIN EN 61000 2 4 class 3 THD max 10 Switch on delay Switch off time 5s Control input DC 0 max 20ms AC 10 max 30ms Re make tome Cyclic operation Control inpu...

Страница 4: ...er supply system the capacitive load is charged to network peak voltage In addition a phase is connected directly to the load This means that the load is under voltage even when switched off and remains connected to the power supply When working on the load disconnection from the network must be made under all circumstances Danger to life Even after disconnection from the network a residual charge...

Страница 5: ...CH compared to conventional technology are High switching speed Switching behavior with low system pollution Switching with no wearing parts Long working life through practically unlimited frequency of operations Areas of application Crane equipment Lifts Welding equipment Molding Wind turbines The power switch can be operated in conjunction with VAr controllers memory programmable controls comput...

Страница 6: ...ted in one direction At maximum load a temperature increase of max 40 C can be expected If temperature sensitive components are used such as cable ducts it is possible that cowls must be provided Distances Fan side 50mm Heat sink outlet 150mm With vertical installation it must be ensured that warm air is always emitted upwards When installing several THYRO SWITCH on top of one another cowls should...

Страница 7: ... THYRO SWITCH Version 1 0 Page 5 EDEBDA0080 1707 1 GB 5 Connection DC gating U2 V2 W2 W1 V1 U1 L1 L2 L3 PE 1 2 3 10 30V DC 230V 115V 4 5 6 AC gating 180 260V AC U2 V2 W2 W1 V1 U1 L1 L2 L3 PE 1 2 3 230V 115V 4 5 6 ...

Страница 8: ...or sign For reactor protected equipment it is absolutely essential that the THYRO SWITCH is connected in series before inductor and capacitor Terminal 1 and 3 For gating with 10 30V DC terminal 1 must be connected to plus and terminal 3 to minus see design DC gating on page 5 Terminal 2 and 3 For gating with 180 260V AC 50 60Hz terminals 2 and 3 must be used see design AC gating on page 5 Terminal...

Страница 9: ...s product see table meets the regulations of Directives 73 23 EEC and 89 336 EEC and complies with the following standards or reference documents EN 61010 1 2002 EN61010 1 B1 2002 EN 61010 1 B2 2004 EN 61000 6 1 2002 EN 61000 6 2 2002 EN 61000 6 3 2002 EN 61000 6 4 2002 Type Voltage Frequency Current TSK40509 400V 50Hz 90A TSK40609 400V 60Hz 90A TSK40511 400V 50Hz 115A TSK40611 400V 60Hz 115A TSK5...

Страница 10: ...THYRO SWITCH User Manual Page 8 Version 1 0 EDEBDA0080 1707 1 GB 9 Notes ...

Страница 11: ...ungsvorschläge Bitte geben Sie die betreffende Anleitung oder Druckschrift mit Versionsnummer und oder Aus gabestand an If you come across misprints in this user manual or printed material please take the time to notify us We will also be glad to hear your ideas notes and suggestions for improvement Please identify the user manual or printed mate rial in question with version number and or revi si...

Отзывы: