![KBR Multimess F96-***-5 Series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/kbr/multimess-f96-5-series/multimess-f96-5-series_quick-manual_659470007.webp)
Rev. 5.00
23892_EDEK
ZA0030-4318-1_EN
7
KBR multimess F96-...-5
Device memory, range of functions
1
Device memory
The device is equipped with internal data memory (fl ash). After uninterrupted
charging (device connected to the power supply) for approx. 100 hours, the
buff er capacitor will have suffi cient charge to protect the internal clock from
failure due to disconnection from the power supply for approx. 7 days.
NOTE
If the capacitor is discharged and it is not connected to a power source, the
time settings will be lost and will need to be reset!
2
Range of functions
The electronic network measuring devices of the multimess F96-... -5 measure
and monitor all important parameters
in a three-phase network and are available in diff erent versions. All device ver-
sions are equipped with a pulse output.
Aside from the multimess F96-0-… -5 entry level model, the load profi le (P+ P- /
Q+ Q-) can be saved with all device versions and later read out via KBR eBus.
Network voltage can be monitored in accordance with EN 61000-4-30. In case
of a violation, the voltage and current history is saved and can be analyzed
on the LCD display. Diff erent optional interfaces and protocols allow various
applications.
2.1
Depending on the optional board (Opt.),
the device has the following functionality:
NOTE
The multimess F96-...-5 is available with diff erent optional boards. Thus, this
user manual describes all options possible. To see which device version you
have, please refer to the nameplate.
Option 0: no optional board
Option 1: optional board with Modbus RS485 capacitor, 2x relay outputs
Option 3: optional board with KBR eBus RS485, Modbus RS485
Option 4: optional board with Modbus Ethernet, 2x relay outputs
Option 5: optional board with Profi bus DP
Option 6: optional board with KBR eBus Ethernet, 2x relay outputs
Option 7: optional board with KBR eBus RS485, Modbus RS485, 2x relay
outputs