Setting ranges
Error message dialog:
No measuring voltage
The settings Message or
No stage power
Alarm relay or Message and
Facility too small
Alarm relay or Off
THD too high
is identical for all errors!
Operating cycle limit exceeded
No measuring current
Light load
Temperature switch-off
Extras:
Display language
German, English, French, Spanish
THD limit
0 to 10%, harmonics monitoring can be disabled (0%)
Sampling rate
Automatic, fixed 50 Hz, fixed 60 Hz
Reset Run
Contrast setting
0 to 10
Brightness setting
0 to 9
Dimmer brightness
0 to 9
Low-load limit
15 mA, 50 mA
Light load delay
1 minute to 60 minutes
Temperature measurement
On / Off
Output 6 or 12
(depending on the controller version) Compensation stage, fan relay
Alarm relay
Error message, fan control
Fan switch on temperature
> 0 °C to 60 °C
Fan switch off temperature
< 0 °C to 60 °C
Switching threshold system off
> 0 °C to 60 °C
System switch on temperature
< 0 °C to 60 °C
Bus mode
Modbus (eBus for production)
Learning mode menu display
On / Off
Key sounds
On / Off