16 

TO CHECK KSM INTERNAL CIRCUIT: 

 

 

If  the  wiring  and  harnesses  are  in  good  order  continue  troubleshooting  by 
unplugging  the  Deutsch  connector  on  the  end-faceplate  of  the  KSM,  giving  you 
access to the pin terminals on the KSM connector.  Refer to pages 10 & 13. 

 

With the circuit breaker reset, using a voltmeter check voltage at Pin #1 of the 
Deutsch four-pin connector and the KSM negative 

-

 ground power stud terminal. If 

voltage is present the circuit is good.  The voltage reading is the actual KAPower 
module voltage and should be at least 10 volts for the 24-volt models and 4 volts for 
the 12-volt models, in order to activate the contactor.  

 

Jump pins 1 and 2 on the four-pin connector, the contactor should activate, you will 
hear a clunk. If not, you may need to remove the KSM cover and check for faulty 
contactor or internal wiring.  Before removing the KSM cover it is recommended 
you contact KBI for assistance. 

 

If  the  circuit  breaker  continues  to  trip  check  the  integrity  of  the  vehicle  or  vessel 
side  of  the  wiring  harness  for  issues  such  as  shorts,  corrosion,  chafing  or  bad 
connections and components.  

 

Check the circuit breaker and contactor relay connections within the KSM module. 
In order to service or replace any of these components you will have to remove the 
cover of the KSM enclosure.  Reference page 5, 

INTRODUCTION: 

Again, contact KBI 

for assistance. 

 

The PLC Module is a sealed unit.  It cannot be serviced.  If additional troubleshooting 
is required contact KBI.

 

STORAGE:

 

The  KAPower  module  should  be  discharged  prior  to  storage  and  for 
prolonged  periods  (>1  year)  should  be  stored  in  a  completely  discharged 

state.  The KSM can be discharged by hooking up the power studs to any resistive load (a 
light bulb or motor of the appropriate voltage) and activating the unit (jump pins 1 and 2 
on  the  four-pin  connector,  the  contactor  should  activate)  until  the  desired  voltage  is 
reached  (6  volts  for  12  volt  systems  and  20  volts  for  24  volt  systems).    Voltage  can  be 
monitored at the power studs. 
The  KAPower  modules  shall  be  stored  within  enclosed  heated  or  unheated  premises 
outfitted  with  a  natural  ventilation  system  in  regions  having  moderate  or  cold  weather 
conditions. Climate control systems are not required. The required  storage temperature 
range is -76º to 185ºF (-60º to 85ºC). 

TRANSPORTATION:

 

The KAPower KSM modules can be shipped in approved corrugated cardboard, wooden, 
or plastic containers. For more information on transportation contact KBI.  

 

 

CAUTION 

Содержание KAPower Starting Module

Страница 1: ...ION MANUAL Gen 3 Rev E KBI Kold Ban International Ltd 8390 Pingree Road Lake In The Hills Illinois 60156 9637 U S A 800 527 8278 847 658 8561 Fax 847 658 9280 www koldban com ATA VMRS T44 KLDBN KBI KAPower 2018 KBI Form 131400 Rev E Gen 3 12 24 Volt ...

Страница 2: ...3 Wiring harness Not Shown 4 Terminal grease Not Shown 5 Protective boots Not Shown ITEMS NEEDED FOR INSTALLATION 1 Battery cables 4 0 cable is recommended 2 Terminals for battery cable 3 Torque wrench with inch socket 4 Minimum 16 gauge wire for harnesses KSM Enclosure DPST Switch ...

Страница 3: ...circuit may follow such a short circuit In case of accidental short circuit ing of the KAPower module or individual capacitors immediately disconnect the KAPower module from the electric circuit Use caution when doing so as short circuited cables can become very hot while spewing melting insulation and copper Noncompliance with the requirements set forth in this Manual may result in KAPower module...

Страница 4: ...__________________________________________ _________________________________________________________ _________________________________________________________ _________________________________________________________ _________________________________________________________ _________________________________________________________ _________________________________________________________ _________...

Страница 5: ...lly Unaffected by Temperatures Increases the Life of Batteries Requires NO Maintenance Safe Easy to Install KAPower Basic Description The KAPower module is an energy storage device KAPower is a High Power device with Low Energy density The cranking or discharge periods will be short but powerful typically less than 30 seconds with the time to full recharge rated in tens of seconds Recharging can b...

Страница 6: ...ovable parts Install the KAPower KSM module as close to the engine s starting batteries or starter as possible Avoid locations that are subject to extreme heat humidity dripping water under deck ventilation systems aboard boats for instance road dirt ice and snow Prevent the external case of the KAPower KSM module from physical impacts Visually inspect the external case prior to mounting the modul...

Страница 7: ...on connections is recommended 5 The quality of the cable connections from the KSM to the vehicle or equipment is critical Make sure to provide good clean robust cable interface connections The cables between the KSM module and the battery do not benefit from over current protection i e they have no fuse or circuit breaker If a short circuit occurs the cable will overheat and it may catch fire or i...

Страница 8: ...s Avoid locations that are subject to extreme heat dripping water humidity road dirt ice and snow While the KSM unit may be mounted in any position or orientation do not mount it directly over batteries or under ventilation systems through which water might drip The internal components of the KSM are IP67 rated but the KSM itself is not IP rated Take care to prevent the external case of the KSM mo...

Страница 9: ...9 10 12 cell KSM The J1939 connector is used for KBI Factory programing only Contact KBI for details ...

Страница 10: ...LLATION PROCEDURE CAUTION KSM Power Stud Nuts should be torqued to 180 Inch Pounds CONNECTORS LOCATED ON THE END FACEPLATE OF THE KSM ENCLOSURE END FACEPLATE OF THE KSM ENCLOSURE The J1939 connector is used for KBI Factory programing only Contact KBI for details Discrete Signal See schematic page 13 Note DPST is wired parallel with OEM start switch connecCons ...

Страница 11: ... circuit to be engaged simultaneously Once the engine starts the Programmable Logic Controller PLC inside the KSM monitors the condition of the KAPower Module and will close or open the Contactor Relay inside the KSM based on the preprogrammed parameters inside the PLC When the engine is stopped the equipment is turned off the contactor opens and the KAPower module remains isolated waiting for the...

Страница 12: ...urced at the engine Install a 5 amp fuse in this circuit within seven 7 inches of the power source Use care not to disturb or compromise the engine s own wiring harness or connections 5 Wire the DPST switch and find and wire the appropriate PLC input pin 4 as based and depicted on the diagram schematic pages 10 13 You will not be connecting any wiring to the J1939 Connector The J1939 CAN Bus is us...

Страница 13: ...us applications where the rear start feature is desired a second DPST Switch can be installed in the rear start location wired in parallel with the front start DPST switch OEM Push Bu on or Key Switch Cranking Start Switch ...

Страница 14: ...power being supplied from both the KSM capacitor module and the standard batteries Once the engine starts and the DPST switch is released the KSM internal PLC module will be active keeping the contactor closed when required allowing the KAPower module to recharge NOTE If the vehicle vessel or equipment s batteries are completely discharged if the battery is dead it may be necessary to keep the DPS...

Страница 15: ...al Check the integrity of the DPST switch and the power supply to the PLC sourced from the engine ignition switched when on wiring harness you created This bi color red green LED is also an indicator for how the KSM is functioning The green side of the LED is connected parallel with the contactor The red side is connected to an output on the PLC as shown in the schematic depicted on page 13 The PL...

Страница 16: ...ker and contactor relay connections within the KSM module In order to service or replace any of these components you will have to remove the cover of the KSM enclosure Reference page 5 INTRODUCTION Again contact KBI for assistance The PLC Module is a sealed unit It cannot be serviced If additional troubleshooting is required contact KBI STORAGE The KAPower module should be discharged prior to stor...

Страница 17: ...the product to be defective under the terms of this warranty it will be replaced without charge Failure due to accident abuse neglect use other than in the intended application specified in this manual improper installation or maintenance mishandling and repairs or attempted repairs which have been made by others are not covered under the terms of this warranty Kold Ban International Ltd shall not...

Страница 18: ...18 Appendix A ...

Страница 19: ...19 TM R R TM R R R TM R R R R M J Burke D R Solberg Appendix B ...

Страница 20: ...20 ...

Отзывы: