14
Table 4 – Electrical Ratings
Model No.
Part No.
Max. HP
AC Line
Voltage
(50/60 Hz)
Phase
(Ø)
Max.
AC Line
Current
(Amps AC)
Fuse or
Circuit
Breaker
Rating
(Amps)
Voltage
Range
(Volts AC)
Max. Load
Current
(Amps/Phase)
Motor
Horsepower
Selection
2
(Jumper J2)
Net Wt.
Gray White
1
HP kW
lbs kg
KBAC-24D
9987 9988 1 0.75
115
1
14.4
20
0 - 208/230
3.6
1
3/4 1/2 1/4 1/8 5.9 2.7
208/230
8.1
15
KBAC-27D
9520 9521
11/2 1.13
115
1
22
25
0 - 208/230
5.5
–
11/2
3
1 3/4 1/2 10.3 4.7
2 1.5 208/230
16.7
20
6.7
2
3
A B C D E
KBAC-29 (1P)
4
10001 10002 3 2.25 208/230
1
20.5
25
0 - 208/230
9
3
2 11/2 1 3/4
10.3 4.7
KBAC-29
9528 9529
2 1.5
208/230
1
16.7
20
0 - 208/230
6.7
–
2
5
11/2 1 3/4
3 2.25
3
11.7
15
9
3
5
KBAC-45
6
9530 9531 3 2.25 400/460
3
7.2
10
0 – 400/460
5.5
3
2 11/2 1 3/4
KBAC-48
6
9540 9541 5 3.75 400/460
3
11
15
0 – 400/460
8.3
5
3
2 11/2 1
A B C
KBAC-217
8868 8879
5 3.75 208/230
3
22.1
25
0 - 208/230
17
5
3
2
22 10
KBAC-217S
8863 8855
KBAC-217F
8861 8853
KBAC-217SF
8869 8880
KBAC-416
8870 8881
10 7.5 400/460
3
20.8
25
0 – 400/460
16
10
7.5 5
KBAC-416S
8864 8856
KBAC-416F
8874 8883
KBAC-416SF
8871 8882
Notes: 1.
White FDA approved finish.
2.
Bold indicates factory setting. On Model KBAC-24D, Jumper J2 is labeled “1”, “3/4”, “1/2”, “1/4”, “1/8” (factory set to the
“1” position).On Model KBAC-27D, Jumper J2 is labeled “2”, “11⁄2”, “1”, “3/4”, “1/2” (factory set to the “11⁄2” position). On Models KBAC-29, 45, 48, Jumper J2 is
labeled “A”, “B”, “C”, “D”, “E” (factory set according to the table).
3.
Model KBAC-27D is rated 11⁄2 HP maximum with 115 Volt AC Line input and 2 HP maximum
with 208/230 Volt AC Line input.
4.
Model KBAC-29 (1P) is rated 9 Amps at 35 °C / 95 °F and derated to 8.3 Amps at 40 °C / 104 °F. For ambient temperatures
above 40 °C / 104 °F, the drive is derated 2.5% per °C.
5.
Model KBAC-29 is rated 2 HP maximum with single-phase AC Line input and 3 HP maximum with
3-phase AC Line input.
6.
Models KBAC-45, 48, KBAC-217 Series and KBAC-416 Series are rated 0 – 400 Volts AC for 50 Hz motor operation and 0 – 460 Volts
AC for 60 Hz motor operation.
Содержание KBAC Series
Страница 34: ...34 Notes...
Страница 35: ...35 Notes...