FIG. 7A – VOLTAGE

FOLLOWING

ii.

Bidirectional operation using reversing contacts – Connect to terminals "10," "11,"
"12," "13" as per fig. 6.

iii. Bidirectional operation with potentiometer – Connect potentiometer to terminals "10,"

"11," "12" as per fig. 6.

FIG. 6 – MAIN SPEED POTENTIOMETER CONNECTIONS

FORWARD

REVERSE

BIDIRECTIONAL

with REVERSING CONTACT

BIDIRECTIONAL

with SPEED POT

F. Voltage Following –

 An 

isolated

 analog voltage can be used in

lieu of main speed potentiometer.  Connect signal to terminals "12"
and "13."  Note:  Terminal "13" is common.  A positive signal with
respect to terminal "13" will produce a positive output to motor.  A
negative signal with respect to terminal "13" will produce a
negative output.  A 0 to ±10VDC is required to operate control
from 0 to ± full output.  

WARNING!  Do not common multiple

drives without a signal isolator.

  A bipolar signal isolator, SI-4X

(KB P/N 8801), is available as an option from your distributor.
(See fig. 7A.)

G. Enable –

  Control may be electronically started and stopped with

Enable circuit.  Connect Enable contacts between terminals "8"
and "9."  When terminals "8" and "9" are joined, control is in "ENABLE" state.  When
terminals "8" and "9" are open, control is in "INHIBIT" state.  (See fig. 7B, p. 10.)

IMPORTANT!  If Enable is not used, a jumper must be installed between terminals
"8" and "9" or control will not operate.  (See Safety Warning on page 1.)

H. Start/Stop Circuit –

  A standard 3-wire start/stop circuit is provided (terminals "5," "6" and

"7").  This allows a remote momentary 2-button start/stop station to be installed.  In this
mode, if AC power is removed, the start button must be used to restart the control.  Also,
when the control is in the Timed Current Limit mode (J6 set to TCL) and has "timed out,"
it must be restarted using the start button.  (See fig. 7C, p. 10)

IMPORTANT!  If the Start/Stop mode is not required, a jumper must be installed
between terminals "5" and "7."

(Note:  The Timed CL function will operate only when the start/stop mode is used.)
Control will not start using Start/Stop circuit if AC line voltage is below 20% of nominal
(190V on 230V circuit).  (See Safety Warning on page 1.)

I.

Alarm Contacts

 –  S.P.S.T. relay contacts (terminals "3" and "4") are used to signal a

warning or to shut other equipment down if control goes to an Inhibit state.  Rating of
contacts are 1A-28VDC, .5A-115VAC.  See table 6 for relay control state vs contact state.
(See fig. 7D, p. 10.)

Содержание 8821

Страница 1: ... 6 7 8 9 10 11 12 13 TB1 CL CL IR COMP RESP MAX SPD OFFSET FWD FWD TCL REV REV EN EN PWR ON CL ACCEL FWD ACCEL REV DB J1 NLT J8 S LT EARTH GND R33 See Safety Warning on Page 1 The information contained in this manual is intended to be accurate However the manufacturer retains the right to make changes in design which may not be included herein A COMPLETE LINE OF MOTOR DRIVES ...

Страница 2: ...ET and TCL trimpots have been moved to be aligned with the other trimpots The General Performance Specifications Electrical Ratings Mechanical Specifications and Connection Diagrams have not changed See the figure below for the Trimpot and Jumper location changes Model KBRG 255 SMT Logic Board Layout ...

Страница 3: ... Information 7 5 Field Connections 7 6 Control State vs Relay Contact State 10 7 Current Limit Timer Settings 13 8 Parts List Power Board 13 9 Parts List Logic Board 15 16 FIGURES 1 Control Layout 3 2A Linear Torque Curve 5 2B Non Linear Torque Curve 5 3 AC Line and Armature Connection 7 4A Full Voltage Field 7 4B Half Voltage Field 7 5 Mechanical Specifications 8 6 Main Speed Potentiometer Connec...

Страница 4: ...ple drives from a non isolated signal source ii SAFETY WARNING PLEASE READ CAREFULLY This product should be installed and serviced by a qualified technician electrician or electrical maintenance person familiar with its operation and the hazards involved Proper installation which includes wiring mounting in proper enclosure fusing or other overcurrent protection and grounding can reduce the chance...

Страница 5: ...w all instructions carefully Fire or electrocution can result due to improper use of this product Read Safety Warning TABLE 1 ELECTRICAL RATINGS Model Part No Input Voltage VAC Max AC Current RMS Output Voltage VDC Max DC Output Current ADC Max Horsepower HP KW KBRG 255 8821 230 38 0 180 25 5 3 8 TABLE 2 GENERAL PERFORMANCE SPECIFICATIONS Parameter Specification Factory Setting AC Line Input Volta...

Страница 6: ...ing of Jumpers and Approximate Trimpot Settings M1 M2 L1 L2 F F TB1 TB2 F1 1 2 3 4 5 6 7 8 9 10 11 12 13 TB1 CL CL IR COMP RESP MAX SPD OFFSET FWD FWD TCL REV REV EN EN PWR ON CL ACCEL FWD ACCEL REV DB J1 NLT J8 S LT EARTH GND R33 DWG C3900 2 00992 ...

Страница 7: ...operation is regeneration the applied load is in the same direction as the direction of motor rotation Table 3 summarizes the different modes of regen operation TABLE 3 SUMMARY OF CONTROL OPERATION Quadrant Type of Operation Motor Rotation Direction Motor Torque Direction Applied Load Direction I Motoring CW CW CCW II Regeneration CCW CW CCW III Motoring CCW CCW CW IV Regeneration CW CCW CW B Torq...

Страница 8: ...ed refer to fig 1 p 3 Bold indicates Factory Setting See sec II p 4 for J7 and J8 settings A J4 Tach generator Voltage Note Selection of the jumper position is not required if armature feedback is used Place J4 jumper in the position 7V 20 30V 50V that corresponds to the tach generator voltage in Volts KRPM Note The tach voltage jumper position is based on motor speed of 1 800 RPM ...

Страница 9: ... Limit NTCL In this mode the drive will reach preset Current Limit during overload and stay at that level until drive is turned off or fuse blows If Non Timed CL is desired move jumper J6 from the factory set TCL position to the NTCL position IV MOUNTING Mount the KBRG 255 in a vertical position connection terminals in down or up position on a flat surface free of moisture metal chips or corrosive...

Страница 10: ...tors with 100VDC fields connect field to terminals F and L1 see fig 4A and 4B See table 5 for summary of Field Connections CAUTION Shunt Wound motors may be damaged if field remains connected without motor rotating for an extended period of time To remove field voltage from motor disconnect AC line FIG 4A FULL VOLTAGE FIELD FIG 4B HALF VOLTAGE FIELD TABLE 5 FIELD CONNECTIONS Shunt Wound Motors Onl...

Страница 11: ...8 FIG 5 MECHANICAL SPECIFICATIONS INCHES mm ...

Страница 12: ...s 8 and 9 are joined control is in ENABLE state When terminals 8 and 9 are open control is in INHIBIT state See fig 7B p 10 IMPORTANT If Enable is not used a jumper must be installed between terminals 8 and 9 or control will not operate See Safety Warning on page 1 H Start Stop Circuit A standard 3 wire start stop circuit is provided terminals 5 6 and 7 This allows a remote momentary 2 button star...

Страница 13: ...mperage fuse 150 amp Littelfuse 3AG normal blo or equivalent which protects the control transformer and other components against catastrophic failure Under normal circumstances this fuse should never blow See fig 1 p 3 for location The KBRG 255 does not contain AC line or armature fusing It is recommended that a 40 Amp fuse or circuit breaker be installed on each AC line conductor not at ground po...

Страница 14: ...es the amount of time it takes the control voltage to reach full output in the reverse direction and the time it takes for the control voltage in the forward direction to reach zero output REV ACCEL is the Forward Decel The FWD and REV ACCEL trimpots are factory adjusted to 1 second The acceleration times are adjustable to a maximum of 15 seconds See fig 8 for graphic representation of ACCEL Note ...

Страница 15: ...series with armature lead Lock shaft of motor iii Apply power Rotate CL trimpot CW until desired CL setting is reached factory setting is 1 5 times rated motor current Be sure control is in Forward direction for FWD CL trimpot adjustment and likewise with REV CL WARNING Do not leave motor shaft locked for more than 2 3 seconds to prevent motor damage CAUTION Adjusting the CL above 150 of motor rat...

Страница 16: ...ime Secs Trimpot Position 1 Full CCW 8 Midway 15 Full CW IX FUNCTION INDICATOR LAMPS A LED 1 Power On PWR ON Indicates that the drive is energized with the AC line B LED 2 Current Limit CL Indicates that the drive is in Current Limit If set in the timed Current Limit mode J6 set to TCL and has timed out the LED 2 will remain ON until the drive is restarted C LED 3 Forward Enable FWD EN Indicates t...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...tee expressed or implied and we are not responsible for any expense including installation and removal inconvenience or consequential damage including injury to any person caused by items of our manufacture or sale Some states do not allow certain exclusions or limitations found in this warranty so that they may not apply to you In any event KB s total liability under all circumstances shall not e...

Отзывы: