H_weather
_Twout
L_weather
_Twout
L_ODU_T4
H_ODU_T4
Shift
value
+05
-05
04:27
27-05-2019
sun
OK
CONFIRM
NO
YES
WEATHER TEMP. SET function is on. Do you want
to turn it off ?
HEAT MODE
WEATHER TEMP. SET
SHIFT VALUE
SCROLL
OFF
0
°C
MULTIPLE
SET POINT
WEATHER
TEMP. SET
PRESET
TEMP.
FCU
5 6
9
10
11
FHL
12
8
4
radiator
1
2
3
6 7
9
Thermostat 1
Thermostat 2
space 2
space 1
space 0
CN22
N MSP1 N
N
MSP2
AL
Thermostat 1
Thermostat 2
14
You can set the following 4 parameters in FOR
SERVICEMAN. (See ''FOR SERVICEMAN''.)
H_ODU_T4: high outdoor temperature (indicates
the high temperature point among outdoor ambient
temperature)
L_ODU_T4: low outdoor temperature (indicates
the low temperature point among outdoor ambient
temperature)
L_weather_Twout: the desired leaving water
temperature when the outdoor temperature equals or
drops below the low ambient temperature (indicates
that the desired water outlet temperature is lower
than the low temperature point of the outdoor ambient
temperature)
H_weather_Twout: the desired leaving water
temperature when the outdoor temperature equals or
rises above the high ambient temperature (indicates
the desired water outlet temperature is higher than
the high temperature point of the outside ambient
temperature)
If Weather TEMP.SET is enabled, you cannot set the
desired water outlet temperature. If you press ▼ or ▲,
the following interface is displayed.
Press
OK
at
NO
to return to the main interface. Move
the cursor to
YES
, and then press
OK
. The weather
temperature curve setting interface is displayed as
follows.
6.1.3 Multiple Set Point Function
When the hydro module is connected to multiple terminals that raise different water temperature requirements, you need
to use the multiple set point function. The multiple set point function is used to set the desired water outlet temperature of
space1 and space2. (For more information, please read the Installation Manual.)
The hydro module will calculate the space that requires energy and operate at the highest water temperature among the
water outlet temperature requirements.
Note: For space 0, water temperature is set on the main interface.