 3

CAUTION 

 

„

Install the outdoor unit at a place where discharge air is not 

blocked. 

 

„

When an outdoor unit is installed in a place that is always exposed 

to a strong wind like a coast or on a high storey of a building, 

secure a normal fan operation by using a duct or a wind shield.

 

„

When installing the outdoor unit in a place that is constantly 

exposed to a strong wind such as the upper stairs or rooftop of a 

building, apply the windproof measures referring to the following 

examples.

 

„

Install the unit so that its discharge port faces to the wall of the 

building. Keep a distance of 2000mm or more between the unit and 

the wall surface. 

2000

Fig.2-1

 

z

Supposing the wind direction during the operation season of the 

discharge port is set at right angle to the wind direction.  

Strong

wind

Strong

wind

Fig.2-2

 

„

Installation in the following places may result in some troubles. Do 

not install the unit in such places below.

 

z

A place full of machine oil.

 

z

A place full of sulphuric gas.

 

z

A place where high-frequency radio waves are likely to be 

generated as from audio quipment, welders, and medical 

equipment.

3.  OUTDOOR UNIT INSTALLATION

3.1  Installation place

Please keep away from the following place, or malfunction of the 
machine may be caused:

•  There is combustible gas leakage. 

•  There is much oil (including engine oil) ingredient. 

•  There is salty air surrounding(near the coast) 

•  There is caustic gas (the sulfide, for example) existing in the air 

(near a hotspring) 

•  A place the heat air expelled out from the outdoor unit can 

reach your neighbor’s window. 

•  A place that the noise interferes your neighbors every day life. 

•  A place that is too weak to bear the weight of the unit 

•  Uneven place. 

•  Insufficient ventilation place.

•  Near a private power station or high Frequency equipment. 

•  Install indoor unit, outdoor unit, power cord and connecting 

wire at least 1m away from TV set or radio to prevent noise or 

picture interference. 

•  Install the unit in the place that can offer enough space for 

installation and maintenance.Don’t install it in the place that has 

a high requirement for noise,such as the bed room.

The insulation of the metal parts of the building and the air conditioner 
should comply with the regulation of National Electric Standard.

 

CAUTION

Keep indoor unit, outdoor unit, power supply wiring and 
transmission wiring at least 1 meter away from televisions and 
radios. This is to prevent image interference and noise in those 
electrical appliances. (Noise may be generated depending on 
the conditions under which the electric wave is generated, even 
if 1 meter is kept.)

3.2  Installation space (Unit:mm)

Fig.3-1

Fig.3-3

Fig.3-2

G

B

A

8kW

F

E

H

D

C

10/12kW

A

G

 

Содержание KMF-120 DVN4

Страница 1: ...chasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Mini Amazon III KMF 80 DVN4 KMF 100 DVN4 KMF 120 DVN4 KMF 140 DVN4 KMF 160 DVN4 INSTALLATION MANUAL ...

Страница 2: ...nnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule The power cord type designation is H05RN R H07RN F or above Ask an authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation m...

Страница 3: ...kW 2 8 Network matching wires 2 9 Connecting pipe 16kW 1 10 L shaped pipe 14kW 1 NOTE z Check if any accessory in the above figure is missing All the accessories must be kept properly z All the fittings should be Kaysun fittings z Wired Remote controller purchase separately z Outlet sealant purchase separately z All the figures in the manual explain only the general appearance and dimensions of th...

Страница 4: ...ne may be caused There is combustible gas leakage There is much oil including engine oil ingredient There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hotspring A place the heat air expelled out from the outdoor unit can reach your neighbor s window A place that the noise interferes your neighbors every day life A place that is too...

Страница 5: ...nlet surface Air inlet surface Maintenance cable and pipeline surface 2000 500 3000 3000 300 600 2000 300 3 3 Moving and installation Since the gravity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 an...

Страница 6: ...utlet plate The method of the out pipe in the same way of the back out pipe Undersurface outlet pipe the knock out should from inside to outside and then piping and wiring through this Pay attention to the piping the fat connecting pipe should out from the largest hole otherwise the pipes will be rubbed Please do the moth proofing for the knocked out hole to avoid the pest processing into and dest...

Страница 7: ...9 5 KCMI 112 160 A 230 Φ19 1 Φ9 5 KCMI 112 4 5 Confirmation for the diameters of outdoor unit connecting pipes R410A outdoor unit connecting pipes diameters Table 4 4 Total capa ctiy of The outdoor units Main pipe size when the total equivalent piping length of liquid air side is 90m Main pipe size when the total equivalent piping length of liquid air side is 90m air side mm liquid side mm The fir...

Страница 8: ...ion please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m z The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its total capacity is 28 2 56 the size of pipe L2 isΦ15 9 Φ9 5 and the branch pipe B should be KCMI 112 The downstream inner units of the main pipe L4 are N3 N4 and its...

Страница 9: ...r Unit Outdoor Unit Drop Height H Outdoor Unit up 10m 8kW 25m 10 12kW 30m 14 16kW Outdoor Unit Down 10m 8kW 20m 10 12kW 20m 14 16kW Indoor Unit to Indoor Unit Drop Heihgt H 8m Note When the total equivalent piping length of liquid gas side is 90m it must increase the size of air side main pipe Besides according to the distance of refrigerant pipe and the over matched state of inner unit when the c...

Страница 10: ...of the vacuum gauge rises If the reading rises there is residual water or gas leakage in the system The leakage must be checked and solved and the test should be performed again z Water may enter into pipes in the following conditions the installation is carried out in rainy seasons and the installation period is long the pipes are condensed inside rainwater enters the pipes z After the above vacu...

Страница 11: ...198 198 198 198 Max V 264 264 264 264 264 MCA 21 25 28 75 35 40 40 TOCA 18 1A 24A 29A 33A 33A MFA 25 32 40 40 40 Compressor MSC Soft star Soft star Soft star Soft star Soft star RLA 9 45 9 45 15 5 15 5 15 5 OFM kW 0 08 0 17 0 17 0 17 0 17 FLA 1 0 1 52 1 52 1 52 1 52 indoor unit power of one system into the same branch circuit z Please put the connective wire system between indoor unit and outdoor ...

Страница 12: ... for 8kW and reserved digital multimeter interface for 10kW 12kW 14kW and 16kW The arrangement of OAE XYE and PQE depends on the unit Note The wired controller and centralized controller in the dashed box are optional accessories If necessary please contact the local distributor for purchase Fig 5 4 IDU IDU IDU IDU ODU P Q E P Q E P Q E Build out resistor Remote controller Wired controller P Q E P...

Страница 13: ...ble 5 3 Rated current of appliance A Nominal cross sectional area mm Flexible cords Cable for fixed wiring 3 0 5 and 0 75 1 to 2 5 3 and 6 0 75 and 1 1 to 2 5 6 and 10 1 and 1 5 1 to 2 5 10 and 16 1 5 and 2 5 1 5 to 4 16 and 25 2 5 and 4 2 5 to 6 25 and 32 4 and 6 4 to 10 32 and 50 6 and 10 6 to 16 50 and 63 10 and 16 10 to 25 5 2 2 The method of fixing the power cord and signal line 1 The method ...

Страница 14: ... connected to the power for 12hr z Test running can not start until all the valves are affirmed open z Never make the forced running Or the protector sits back danger will occur 7 PRECAUTIONS ON REFRIGERANT LEAKAGE This air conditioner A C adopts inncouous and nonflammable refrigerant The locating room of the A C should big engough that any refrigerant leakage is unable to reach critical thickness...

Страница 15: ...or equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more at least every three months or wh...

Страница 16: ......

Отзывы: