14
NOTE
Please press “constraint cool” button to carry out refrigerant
recycling process. Keep the low pressure above 0.2MPa, other
wise compressor may be burnt out.
7.1 Important information for the used
refrigerant
This product has the fluorinated gas, it is forbidden to release to air.
Refrigerant type: R410A; Volume of GWP: 2088;
GWP=Global Warming Potential
Model
Factory charge
Refrigerant/kg
tonnes CO2 equivalent
8kW
2.20
4.59
10kW
2.35
4.91
12kW
3.00
6.26
14kW
3.40
7.10
16kW
3.80
7.93
Attention:
Frequency of Refrigerant Leak Checks
1) For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes of CO2 equivalent or more,but of less than 50
tonnes of CO2 equipment,at least every 12 months, or where
a leakage detection system is installed, at least every 24 months.
2) For equipment that contains fluorinated greenhouse gases in
quantities of 50 tonnes of CO2 equivalent or more,but of less than
500 tonnes of CO2 equipment,at least every six months, or where a
leakage detection system is installed, at least every 12 months.
3) For equipment that contains fluorinated greenhouse gases in
quantities of 500 tonnes of CO2 equivalent or more,at least every
three months, or where a leakage detection system is installed,
at least every six months.
4) Non-hermetically sealed equipment charged with fluorinated
greenhouse gases shall only be sold to the end user where
evidence is provide that the installation is to be carried out by an
undertaking certified person.
5) Only certificated person is allowed to do installation, operation and
maintenance.
8. TURN OVER TO CUSTOMER
The owner’s manual of indoor unit and owner’s manual of outdoor or
unit must be turned over to the customer. Explain the contents in the
owner’s manual to the customers in details.
16100101A04593 V.H