16
8.4 Electric wiring
8.4.1 Electric wiring
•
The air-conditioner should apply special power supply, whose voltage should conform to rated voltage.
•
Wiring construction must be conducted by the professional technicians according to the labeling on the circuit diagram.
•
The power wire and the grounding wire must be connected to the suitable terminals.
•
The power wire and the grounding wire must be fasten up by suitable tools.
•
The terminals connected the power wire and the grounding wire must be fully fastened and regularly checked, in case to
become loose.
•
Only use the electric components specified by our company, and require installation and technical services from the
manufacturer or authorized dealer. If wiring connection doesn't conform to electric installation specification, it may cause
many troubles like failure on controller, electronic shock and so on.
•
The connected fixed wires must be equipped with full switching-off devices with at least 3mm contact separation.
•
Set leakage protective devices according to the requirements of national technical standard about electric equipment.
•
After completing all wiring construction, conduct careful check before connecting the power supply.
•
Please carefully read the labels on the electric cabinet.
•
Please don't repair the controller by yourself, since improper operation may cause electric shock, damages to the
controller and other bad results. If the unit need repair, please contact the maintenance center., since improper repair
may cause electric shock, damages to the controller, and so on. If the user has any requirement of repair, please contact
the maintenance center.
•
The power cord type designation is H07RN-F.
CAUTION
8.4.2 65KW and 110KW
DIP switch, buttons and digital display positions of uints.
DSP1
DSP2
ENC1
S1
S2
S3
S4
Fig. 8-7 Display positions
8.4.3 DIP switch instructions
Table 8-4 65KW and 110KW
ENC1
0-F
0-F valid for uint address setting on
the DIP switches
0 indicates the master unit and 1-F
the auxiliary uints
(parallel connection) (0 by default)
S1-1
OFF
Normal control
Valid for S1-1 OFF (factory default)
ON
Remote control
valid for S1-1 ON
S1-2
OFF
Normal outlet water temperature
Valid for S1-2 OFF
ON
High outlet water temperature valid
for S1-2 ON (factory default)
S1-3
OFF
Single water pump control
Valid for S1-3 OFF (factory default)
ON
Multiple water pumps control
Valid for S1-3 ON
S1-4
OFF
Single variable frequency pump
control of unit valid for S1-4 OFF
(factory default)
ON
Frequency conversion pump plus
constant frequency pump control of
unit valid for S1-4 ON.
S3-1
ON
Valid for S3-1 ON (factory default )
S4
0010
DIP switch for capacity selection
(65KW defaults 0010)
0101
DIP switch for capacity selection
(110KW defaults 0101)