01
ACCESSORIES
Unit
Installation & Operation Manual
Temperature testing components
of total water outlet
Transformer
Installation manual of
wired controller
Quantity
1
1
1
1
Shape
Purpose
/
Use for installation (only need for setting the main module)
1 INTRODUCTION
1.1 Use conditions of the unit
1) The standard voltage of power supply is 380-415V 3N~50Hz, the minimum allowable voltage is 342V, and the maximum voltage
is 456V.
2) To maintain better performance, please operate the unit under the following outdoor temperature:
-15
-20
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
0
5
10
15
20
25
30
T4
[°
C]
-25
-30
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
20
25
30
35
40
45
50
55
60
65
70
T4
[°
C]
65KW&110KW
COOLING
Two [°C]
Two [°C]
Outlet water temperature (°C)
Outlet water temperature (°C)
Fig. 1-1-1 Cooling operating range
Fig. 1-1-2 Heating operating range
65KW&110KW
HEATING
Low leaving water temperature mode can be set by wired controller, please refer to the Operation Manual (select “LOW
OUTLETWATER CONTROL” under “SERVICE MENU” page) for details. If low leaving water temperature function is effective, the
operation range will extend to the shadow area. When the setting water temperature is less than 5
°
C, antifreeze liquid (concentration
above 15%) should be added in the water system, otherwise the unit and the water system will be damaged.
Domestic hot water mode can be set by wired controller, please refer to the Operation Manual (select “DHW SWITCH” under “USER
MENU” page) for details. The outlet temperature of the heat pump can reach 62
°
C when it is run alone, and the outlet temperature
can reach 70
°
C when it is paired with the electric auxiliary heating.