30
No. Code Content
Note
37
HE
1HE No inset A valve error
Recovered upon error recovery
2HE No inset B valve error
Recovered upon error recovery
3HE No inset C valve error
Recovered upon error recovery
38
F0
1F0 IPM module A transmission error
Recovered upon error recovery
2F0 IPM module B transmission error
Recovered upon error recovery
39
F2 Superheat insufficient
Wait at least 20min before recovering
40
F4
1F4 module A L0 or L1 protection occurs for 3 times in 60 minutes Recovered by power off
2F4 module B L0 or L1 protection occurs for 3 times in 60 minutes Recovered by power off
41
F6
1F6 A system bus voltage error (PTC)
Recovered upon error recovery
2F6 B system bus voltage error (PTC)
Recovered upon error recovery
42
Fb Low pressure sensor error
Recovered upon error recovery
43
Fd Suction temperatrue sensor error
Recovered upon error recovery
44
FF
1FF DC fan A error
Recovered by power off
2FF DC fan B error
Recovered by power off
45
FP DIP switch inconsistency of multiple water pumps
Recovered by power off
46
C7 If PL occurs 3 times in 100 minutes, the system reports the C7
failure
Recovered by power off or Wired controller clear
fault
47
xL0 Compressor inverter module protection (x=1or 2, 1 for
Compressor A,2 for Compressor B)
Recovered upon error recovery
48
xL1 low-voltage protection (x=1or 2,1 for Compressor A, 2 for
Compressor B)
Recovered upon error recovery
49
xL2 high-voltage protection (x=1or 2,1 for Compressor A, 2 for
Compressor B)
Recovered upon error recovery
50
xL4 MCE error (x=1or 2,1 for Compressor A, 2 for Compressor B)
Recovered upon error recovery
51
xL5 zero-speed protection (x=1or 2,1 for Compressor A, 2 for
Compressor B)
Recovered upon error recovery
52
xL7 phase loss (x=1or 2,1 for Compressor A, 2 for Compressor B)
Recovered upon error recovery
53
xL8 frequency change over 15Hz (x=1or 2,1 for Compressor A, 2 for
Compressor B)
Recovered upon error recovery
54
xL9 frequency phase difference 15Hz (x=1or 2,1 for Compressor A, 2
for Compressor B)
Recovered upon error recovery
55
dF Defrosting prompt
Flash when entering the defrosting
56
L10 Overcurrent protection
Overcurrent fault
L11 Transient phase current overcurrent protection
L12 Phase current overcurrent lasts 30s protection
57
L20 Module over temperature protection
Over temperature fault
58
L30 Low bus voltage error
Power fault
L31 High bus voltage error
L32 Excessively high bus voltage error
L34 Phase loss error
59
L43 Phase current sampling bias abnormal
hardware fault
L45 Motor code not match
L46 IPM protection
L47 Module type not match
60
L50 Startup failure
Control fault
L51 Out of step error
L52 Zero speed error
61
L60 Fan motor phase loss protection
Diagnostic fault
L65 IPM short circuit error
L66 FCT detection error
L6A Open circuit of U-phase upper tube
L6B Open circuit of U-phase lower tube
L6C Open circuit of V-phase upper tube
L6D Open circuit of V-phase lower tube
L6E Open circuit of W-phase upper tube
L6F Open circuit of W-phase lower tube