background image

Manifold Gauge

Pressure gauge

Compound gauge

High pressure 

valve

-76cmHg

Charge hose

Low pressure valve

Vacuum  

pump

Low pressure valve

Pressure hose/

Charge hose

Flare nut

Cap

Valve stem

Valve body

 Page 30 

10. Air Evacuation

Preparations and Precautions

Air and foreign matter in the refrigerant circuit can cause 

abnormal rises in pressure, which can damage the air 

conditioner,  reduce  its  efficiency,  and  cause  injury.  Use 

a vacuum pump and manifold gauge to evacuate the 

refrigerant circuit, removing any non-condensable gas 

and moisture from the system
Evacuation should be performed upon initial installation 

and when unit is relocated.

BEFORE PERFORMING EVACUATION

 

5

Check to make sure the connective pipes between 

the indoor and outdoor units are connected properly.

 

5

Check to make sure all wiring is connected properly.

Evacuation Instructions

1.  Connect the charge hose of the manifold gauge to 

service port on the outdoor unit's low pressure valve.

2.  Connect another charge hose from the manifold 

gauge to the vacuum pump.

3.  Open the Low Pressure side of the manifold gauge. 

Keep the High Pressure side closed.

4.  Turn on the vacuum pump to evacuate the system.

5.  Run the vacuum for at least 15 minutes, or until 

the  Compound  Meter  reads  -76cmHG  (-105Pa)  del 

sistema.

6.  Close the Low Pressure side of the manifold gauge, 

and turn off the vacuum pump.

7.  Wait for 5 minutes, then check that there has been no 

change in system pressure.

8. 

If there is a change in system pressure, refer to Gas 

Leak Check section for information on how to check 

for leaks. If there is no change in system pressure. 

unscrew the cap from the packed valve (high pressure 

valve).

9.  Insert hexagonal wrench into the packed valve (high 

pressure valve) and open the valve by turning the 

wrench in a 1/4 counterclockwise turn. Listen for 

gas to exit the system, then close the valve after 5 

seconds.

10. 

Watch the Pressure Gauge for one minute to make 

sure that there is no change in pressure. The Pressure 

Gauge should read slightly higher than atmospheric 

pressure.

11.  Remove the charge hose from the service port.Utilice 

una llave hexagonal para abrir al máximo la válvula 

de alta presión y la válvula de baja presión.

12. Using hexagonal wrench, fully open both the high 

pressure and low pressure valves.

13. Tighten valve caps on all three valves (service port, 

high pressure, low pressure) by hand. You may 

tighten it further using a torque wrench if needed..

OPEN VALVE STEMS GENTLY

When opening valve stems, turn the hexagonal wrench 

until it hits against the stopper. Do not try to force the 

valve to open further.

Содержание KAY-CF 26 DR9

Страница 1: ...R11 AKAY CF 52 DR11 AKAY CF 71 DR11 IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please ch...

Страница 2: ...ns 4 Owner s Manual 1 Unit Specifications and Features 7 1 Indoor unit display 7 2 Operating temperature 8 3 Other features 8 4 Setting angle of airflow 9 5 Manual operation without Remote 10 2 Care a...

Страница 3: ...7 Wrap piping and cables 22 8 Mount indoor unit 23 8 Outdoor Unit Installation 24 1 Select installation location 24 2 Install drain joint 24 3 Anchor outdoor unit 25 4 Connect signal and power cables...

Страница 4: ...in places near or around combustible gases Emitted gas may collect around the unit and cause explosion Do not operate your air conditioner in a wet room such as a bathroom or laundry room Too much ex...

Страница 5: ...E NOTE OF FUSE SPECIFICATIONS The air conditioner s circuit board PCB is designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board such as...

Страница 6: ...aging of the outdoor unit 2 Installation service maintenance and repair of this unit must be performed by a certified technician 3 Product uninstallation and recycling must be performed by a certified...

Страница 7: ...R ON is set FRESH SWING TURBO or SILENCE feature is turned on OF for 3 seconds when TIMER OFF is set FRESH SWING TURBO or SILENCE feature is turned off cF when anti cold air feature is turned on dF wh...

Страница 8: ...low 0 C 32 F we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance NOTE Room relative humidity less than 80 If the air conditioner operates in excess of th...

Страница 9: ...ill increase the temperature by 1 C 2 F after 1 hour and will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by 1 C 2 F after 1 hour and wil...

Страница 10: ...To restore regular operation use the remote control to activate the unit Unit must be turned off before manual To operate your unit manually 1 Locate the MANUAL CONTROL button on the right hand side o...

Страница 11: ...r Air Filter A clogged air conditioner can reduce the cooling efficiency of your unit and can also be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of t...

Страница 12: ...isplay To reset the reminder press the LED button on your remote control 4 times or press the MANUAL CONTROL button 3 times If you don t reset the reminder the CL indicator will flash again when you r...

Страница 13: ...rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the i...

Страница 14: ...rvice center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a rep...

Страница 15: ...ating performance The voltage is too high or too low Install a manostat to regulate the voltage Cold air entering through doors and windows Make sure that all doors and windows are closed during use C...

Страница 16: ...holder optional 1 Mounting plate 1 Fixing screw for remote controller holder optional 2 Anchor 5 8 dependinf on model Small Filter Need to be installed on the back of main air filter by the authorized...

Страница 17: ...ation Location Determine Wall Hole Position Attach Mounting Plate Drill Wall Hole Connect Piping Connect Wiring Prepare Drain Hose Wrap Piping and Cable Mount Indoor Unit Page 17 5 Installation Summar...

Страница 18: ...ounting Plate 2 Front Panel 3 Power Cable Some Units 4 Louver 5 Functional Filter On Back of Main Filter Some Units 6 Drainage Pipe 7 Signal Cable 8 Refrigerant 9 Remote Controller 10 Remote Controlle...

Страница 19: ...cable and refrigerant piping that connect the infoor and outdoor units The default position for all piping is the right side of the indoor unit while facing the unit However the unit can accomodate p...

Страница 20: ...t the unit 2 If the wall hole is behind the unit keep the knock out panel in place If the wall hole is to the side of the indoor unit remove the plastic knock out panel from that side of the unit This...

Страница 21: ...ower supply stop work immediately Explain your reasoning to the client and refuse to install the unit until the safety issue is properly resolved 4 Power voltage should be within 90 110 of rated volta...

Страница 22: ...he unit remove the plastic panel on the bottom left hand side 5 Feed the signal wire through this slot from the back of the unit to the front 6 Facing the front of the unit connect the wire according...

Страница 23: ...the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate...

Страница 24: ...ion that is exposed to large amounts of dust In a location exposed to a excessive amounts of salty SPECIAL CONSIDERATIONS FOR EXTREME WEATHER If the unit is exposed to heavy wind Install unit so that...

Страница 25: ...ation base of the unit according to the dimensions below Outdoor Unit Dimensions mm Mounting Dimensions A x H x F Distance A mm Distance B mm 681 x 434 x 285 26 8 x 17 1 x 11 2 460 18 1 292 11 5 700 x...

Страница 26: ...on the inside of the wiring cover WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK TURN OFF THE MAIN POWER TO THE SYSTEM 1 Prepare the cable for connection USE THE RIGHT CABLE Indoor Power Cab...

Страница 27: ...frigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and minimize the need for future maintenance 1 Measure the distance between the indoor and outdoor u...

Страница 28: ...is fully flared 8 Remove the flaring tool and flare form then inspect the end of the pipe for cracks and even flaring Step 4 Connect pipes When connecting refrigerant pipes be careful not to use exce...

Страница 29: ...the table above Instructions for Connecting Piping to Outdoor Unit 1 Unscrew the cover from the packed valve on the side of the outdoor unit 2 Remove protective caps from ends of valves 3 Align flared...

Страница 30: ...r at least 15 minutes or until the Compound Meter reads 76cmHG 105Pa del sistema 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that t...

Страница 31: ...outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the following formula ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Met...

Страница 32: ...resistance tester Grounding resistance must be less than 0 1 DURING TEST RUN Check for Electrical Leakage During the Test Run use an electroprobe and multimeter to perform a comprehensive electrical...

Страница 33: ...CONNECTIONS During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double ch...

Страница 34: ...ange without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the lates...

Страница 35: ......

Страница 36: ......

Отзывы: