5)  Filter installing at the unit inlet. In terms of the unit with duct, filter  

in there must be put on the position of duct inlet. (Fig.3-8/3-9) 

NOTE 

The resistance of duct will decrease air-flow-rate, which will  

lead to capacity of unit decreased.  

 Filter inlet 

oulet 

For the case of unit with duct, the duct total length should be no  

more than 5m or the maximums static pressure should be within  

25Pa, and the quantity of bending should be no more than 5. 

For unit air outlet with duct, when unit operating, condensate  

will be generated around outside of duct. Please pay attention to  

the drainage work, we suggest to wrap the thermal insulated  

layer around outside of the duct.  

It is recommended to install the unit in the indoor space, it is not  

allow to install the unit at the rainy space. 

Fig.3-8 

ΦD 

Rain 

 Filter 

Owner should install  
the filter by self; and  
the mesh size is  
about 1.2mm. 

Unit 

Fig.3-9 

Fig.3-6 

6)  To smoothly drain condensate from unit, please install the unit at  

a horizontal floor. Otherwise, please ensuring the drain vent is at  

the lowest place. Recommending the inclination angle of unit to  

the ground should be no more than 2°. 

Rain 

Weather shed 

Drain 

Unit 

Fig.3-7 

WARNING 

Drain 

In case of rain entering to internal components of the unit, the  

component might be damaged or causing physical danger. 

(Fig.3-6) 

In terms of the unit connect with duct reaching to outdoor, a  

reliable  water-resistant  measure  must  be  conduct  on  the  

duct,  to  prevent  water  from  dropping  into  internal  of  the  

unit.(Fig.3-7) 

Fig.3-10 

Installation & Owner‘s Manual 

Содержание COMPAK KHP 15/190 ACS1

Страница 1: ...S MANUAL ALL IN ONE Type Air source Heat Pump Water Heater COMPAK KHP 15 190 ACS1 Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it fo...

Страница 2: ...MD14IU 029DW 202000172619...

Страница 3: ...being The wiring must be performed by professional technicians in accordance with national wiring regulations and this circuit diagram An all pole disconnection device which has at least 3mm separatio...

Страница 4: ...Water Outlet Cover Electric Heater Electric Heater Water Inlet Drain Pipe When ordering repair parts please always give the following information 1 Model serial and product number 2 Parts name NOTE Al...

Страница 5: ...ta will show more details You may be killed or seriously injured DANGER immediately if you don t obey instructions WARNING The unit must be earthed effectively A creepage breaker must be installed adj...

Страница 6: ...water condensation Drain pipe for water condensation Before cleaning be sure to stop the operation and turn the breaker off or pull out the power plug Otherwise an electric shock and injury may be cau...

Страница 7: ...Hot spring area where corrosive gases exist e g sulphide gas Factories where the power voltage fluctuates seriously Inside a car or cabin The water heater must be located in a space 15m and must have...

Страница 8: ...using the tank When water flow smoothly out from water outlet pipe tap water outlet the tank is full turn off all valves and check pipeline to make sure there is no any leakage CAUTION 4 If the inlet...

Страница 9: ...could charge fresh air into room 2 Air inlet without duct air outlet connects to duct A 5m 4 Duct Description A Air outlet Table3 1 Air inlet Round duct Rectangle duct Duct Dimension mm 160 160X160 2...

Страница 10: ...It is recommended to install the unit in the indoor space it is not allow to install the unit at the rainy space Fig 3 8 D Rain Filter Owner should install the filter by self and the mesh size is abou...

Страница 11: ...Electric Heater Item Content Fan capacity Terminal base Transformer Connected wires inside of the tank Zero phase electricity mutual inductor AC mutual inductor Relay connecting wires Relay Without D...

Страница 12: ...ion Solar Input 300L ON OFF SW2 Factory Setting for 190L 300L Model Selection High Pressure Switch Transformer Panel Display Panel Display T5L Lower T5U Upper T3 Evaporator T4 Ambient Th Comp Tp Comp...

Страница 13: ...ration 1 GND Wiring size and connections comply with all local applicable codes and the requirements of this manual Power Cable with Creepage Breaker Water heater and electrical supply are properly gr...

Страница 14: ...installation 8 Sufficient inlet water pressure between 0 15MPa and 0 65MPa Water out Fig 4 1 4 2 2 About Running CAUTION 1 System Structure Figure Unit has two kinds of heat sources heat pump compress...

Страница 15: ...se manually activate E heater Restart After a Long Term Stop When the unit is restarted after a long term stop trail running included it is normal that outlet water is unclean Keep the tap on and the...

Страница 16: ...pressor Last error code ON OFF 8 Previous 1st error or protection code 9 Fig 5 1 Previous 2nd t error or protection code 10 11 5 2 Display Explanation Software number SET SET CLOCK DAY 1 2 ON 3 4 ON 5...

Страница 17: ...s celsius will be lightened will show celsius degree If setting temperature unit as Fahrenheit will be lightened will show Fahrenheit degree Press for 10sec it will change between and No Icon Descript...

Страница 18: ...ally ON 1 The moment of Manually ON has priority 2 The moment of Timer OFF has priority Set the hour value of timer Confirm the hour value of timer Then the minute value of timer will flash slowly CAN...

Страница 19: ...ess button disinfect clock setting Then icon flash and icon will be lightened for 3sec to enter will Press button for and the hour value of clock will flash slowly 1s or no button operation for 30s th...

Страница 20: ...unt of hot water can be tapped A Because the upper water sensor is located on the upper 1 4 tank when tapping hot water out it means there is at least 1 4 tank of hot water available 1 Public water su...

Страница 21: ...out clock menmory so it is needed to reset clock when power put on again EF Clock chip error If necessary contact a qualified person to service the unit Ed P2 E EPROM chip error Contact a qualified pe...

Страница 22: ...Operate the hander of PT valve to ensure that waterways are clear Clean the air filter every month in case of any inefficiency on the heating performance In terms of the filter set in air inlet direct...

Страница 23: ...adjustable Water side exchanger Inlet pipe Dia Outlet pipe Dia Drain pipe Dia PT valve Dia The test conditions Ambient temperature 15 12 C DB WB Water temperature from 15 C up to 45 C Installation Ow...

Страница 24: ......

Отзывы: