2. View or Adjust the 4–20 mA Fault Mode Configuration
The 4-20 mA output is used to monitor the analog data from the sensor, such as a self-test fault. The 4-20
mA output can be programmed for a v
alue of 3.0 mA or 21 mA.
Notes:
For more general information on fault conditions, see
Section 7 “Troubleshooting”
.
To View or Adjust the Fault Current:
1
.
Press and release
SET
until the
Fault
LED is on solid; the
Run Mode
LED will be off.
2.
The
Thermal Signal Bar
Graph shows the 4-20 Fault Mode.
For
3.0 mA the 0-25% LED’s are on solid;
for
21
mA the 75-1
00% LED’s are on solid.
3.
To adjust the Mode, press and release the
Left
or
Right Arrow
keys.
4.
When satisfied with your configuration, press and release
SET
to continue to the next programmable
v
ariable OR press and release
RUN
to return to
Run Mode
.
Thermal Signal
1 00%
0
Relay 1
Relay 2
Fault
Set Point 1
Set Point 2
Run Mode
Bypass
RUN
SET
1
2
CLASSIC
™
Fault LED is On
Left = LOW Right = HIGH
Set Relay Mode HIGH
Set Fault Mode LOW
Figure 1
6 – 4-20 mA Fault Mode Configuration
RUN
adv
ances to Run Mode
SET
adv
ances to next Setup step
Run Mode
LED is Off in Setup Mode
25472-1 01 -V1 A-JF00-W0010 Rev 02