Delivery and handling
Transport
The FIL-SPL must be transported and stored vertically in a dry place. The FIL-SPL boiler should be lifted only
from the lifting point on top of the boiler.
Physical installation
Mount FIL-SPL boiler on a firm base that can take the weight, preferably on a concrete floor or foundation.
The boiler must be mounted in an upright position and bolted on the floor, preferably in a dry and warm
space with a floor drain.
A clearance of approximately 300-500 mm must be left behind the boiler for pipe connections and for
ventilation. According to safety regulations, at least 1 meter of free space must be left in front of the boiler.
With models from 31.5 to 300 kW, either side of the boiler may be close to a wall. With these models,
approximately 1 meter space should be left above the boiler for possibly replacing resistor elements.
With models from 400 to 1600 kW, there must be left space for possibly replacing resistor elements that
are located on one side that is depending on construction. With these models pipe and electrical
connections are on the top of the boiler and thus requires space.
Note! When selecting mounting location, bear in mind that pipe installations, control valves and other
plumping arrangements needs also space.
Note! Leave enough space for servicing boiler and external circulation pump.
Supplied components
Jäspi current transformers can be ordered as an accessory. The Jäspi current transformers can be used as
secondary current transformers for load monitoring of main fuses or for observation of internal power
consumption for alarm. If both properties are needed, one set of Jäspi current transformers and one extra
Jäspi current transformer must be ordered. The transform ratio of Jäspi current transformers is 300/1.
Содержание FIL-SPL
Страница 43: ...Electrical circuit diagrams models of 31 112 kW ...
Страница 44: ......
Страница 45: ......
Страница 46: ...Electrical circuit diagrams models of 150 300 kW ...
Страница 47: ......
Страница 48: ......
Страница 49: ...Electrical circuit diagrams models of 400 1600 kW ...
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 53: ...We reserve rights to changes Kaukora Ltd 2019 D106159 r4 0 ...