External control voltage (input) values and corresponding power steps in different modes.
The function must be selected from the setup menu. Note that the max. setting values are overruling, i.e. if maximum number of power steps has been
limited to 5, the control unit will not enable power steps above 5 even though the external control voltage indicates higher power.
Power
Power
Power Inv.
Power Inv.
Temp.
Model 15
Model 7
Model 15
Model 7
[V]
[Pwr step]
[V]
[Pwr step]
[V]
[Pwr step]
[V]
[Pwr step]
[V]
[°C]
0,00
0
0,00
0
0,00
15
0,00
7
0,00
20,00
0,70
1
1,50
1
0,60
14
1,30
6
1,50
30,00
1,40
2
2,80
2
1,30
13
2,60
5
2,90
40,00
2,00
3
4,00
3
1,90
12
3,90
4
4,00
50,00
2,60
4
5,20
4
2,50
11
5,20
3
5,80
60,00
3,20
5
6,50
5
3,20
10
6,50
2
7,30
70,00
4,00
6
8,00
6
3,90
9
8,00
1
8,70
80,00
4,60
7
10,00
7
4,50
8
10,00
0
10,00
90,00
5,20
8
5,10
7
11,50
99,00
5,90
9
5,70
6
6,50
10
6,30
5
7,20
11
6,90
4
7,80
12
7,50
3
8,50
13
8,20
2
9,20
14
9,00
1
9,80
15
10,00
0
Maximum current of 0 - 10 V external control voltage is 1 mA.
Содержание FIL-SPL
Страница 43: ...Electrical circuit diagrams models of 31 112 kW ...
Страница 44: ......
Страница 45: ......
Страница 46: ...Electrical circuit diagrams models of 150 300 kW ...
Страница 47: ......
Страница 48: ......
Страница 49: ...Electrical circuit diagrams models of 400 1600 kW ...
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 53: ...We reserve rights to changes Kaukora Ltd 2019 D106159 r4 0 ...