Telephone: 1 (450) 444-2030
•
Toll free: 1 (888) 222-1560
•
Fax: 1 (450) 444-2029
•
Internet: www.kantech.com
2006 Tyco Safety Products, Canada, Ltd. All rights reserved
•
Specifications may change without notice
page 33 of 39
DN1656
-
0606
Configuring a DHCP Address (WAN)
Six steps are required to configure the KT-NCC in a wide area network (WAN) using a reserved DHCP
address:
•
Initialize the KT-NCC in factory reset mode.
•
verify the port forwarding configuration with the Network Administrator.
•
connect the KT-NCC to the network.
•
register the KT-NCC to the EntraPass Global Edition server.
•
enter TCP/IP parameters in the EntraPass server.
•
configure the KT-NCC in EntraPass Global Edition.
Initializing the KT-NCC in Factory Reset Mode
A factory reset will delete the entire configuration of the KT-NCC, including the IP address. It is recommended to
reinitialize the KT-NCC before starting the configuration.
1.
Use needle nose pliers to remove jumpers
JP2
and
JP3
(see Figure 5: KT-NCC Connections Diagram
on page 9).
2.
Press
Reset
.
3.
Reinstall
jumpers JP2
and
JP3
.
Port Forwarding
After collecting the network information necessary to configure the system from the Network Administrator,
ensure that the routers are well configured (port forwarding).
•
Port forwarding configuration is only done on static IP or reserved DHCP addresses.
•
Port forwarding is done to the same IP address. If you use more than one KT-NCC with a router, you
should use different ports for every KT-NCC.
To help you understand how to configure routers, please refer to the diagram on page 32.
Site Server Router (Router No. 1)
•
Ensure that port 18701 is well forwarded to the address of the EntraPass server (no 1 in the
diagram on page 32).
•
Ensure that UDP protocol is selected.
KT-NCC Site Router (Router No. 2)
•
Ensure that the port at no 15 in the diagram on page 32 is well forwarded to the KT-NCC address.
•
Ensure that UDP protocol is selected.
Connecting the KT-NCC
1.
Connect the network cable to Ethernet port #1 of the KT-NCC.
•
The blue pilot light (Vital LED) of the KT-NCC will blink quickly to signal that the controller is in
reset mode.
•
The blue pilot light (Vital LED) of the KT-NCC will remain lit for 15 seconds to signal that the
controller is in start mode.
•
The blue pilot light (Vital LED) of the KT-NCC will blink once/second to signal that the controller
has been reset but it is not yet registered on the EntraPass server. The KT-NCC is in factory default
mode.
Note: