www.kg-groep.com page 3
1
F
OREWORD
This
owner9s
manual must be thoroughly read and understood before using and operating the NANO
MAR SYSTEM and is intended for end users. The NANO MAR SYSTEM and the associated connections
must be installed, commissioned, and maintained by a skilled, knowledgeable, and competent person
or organization that is appropriately qualified to perform this work and is familiar with the objective
of the equipment and the associated technical terminology.
2
C
ERTIFICATION
The NANO MAR SYSTEM has successfully passed CE and FCC, EMC testing according to EN 50130, EN
61000, EN 55016, 47 CFR15-ICES-003, ANSI 63.4, IEC60945-pt11 and a DNV marine type approval
according the DNV Class Guideline 0339-2021, certificate TAA000037H. For that the NMS has endured
extensive environmental tests such as vibration, dry heat, damp heat and cold tests in accordance
with the requirements of the DNV-CG 0339 standard.
3
I
NTRODUCTION
The purpose of the NANO MAR SYSTEM is to control and monitor a number of aerosol generators
mounted on a ship as part of a fire extinguishing system. The NANO MAR SYSTEM is a compact and
robust stand-alone fire detection-extinguishant release system designed to protect various
applications like electrical cabinets, engine rooms in vessels, yachts and other small areas or
equipment. The NANO MAR SYSTEM continuously senses its inputs and, in the event of a fire, gives
the correct output to enable a product specific fire extinguishing. The NANO control panel has two
fire detection zones, any, or all of which can contribute to the extinguishant release decision. In a
marine application, it
9s
NOT common for a fire suppression system to be released by automatic fire
detector. By default, the NANO control panel is set to only manual release, but can also be changed
to automatic & manual release via push buttons on the NANO control panel.
4
M
AINTENANCE
&
C
LEANING
There are not user-replaceable parts in the NANO MAR SYSTEM. Take Electrostatic Discharge (ESD)
precautions when opening the NANO control panel or NANO ETB BOX. Avoid direct contact with any
of the components or connectors connected to the printed circuit board. Failure to follow accepted
ESD handling practices could cause damage to the NANO MAR SYSTEM. Before starting the cleaning
process, bring the system out of operation to prevent an unwanted fire extinguishing system release.
It is important to note that improper cleaning of the NANO control panel front can damage this panel
inhibit their ability to sense fire and activate the fire extinguishers. To remove dust and contaminants,
use nonalcoholic
products which has been designed for that purpose.
Do not use high pressure or stream cleaners
.