TECHNICAL DESCRIPTION
ULTRAFLOW
®
54 and 34
5512-385 GB/02.2014/Rev. H1
13
4.6
Pulse Divider configuration CCC-DD-E-MMM
Pulse Divider is configured for ULTRAFLOW
®
meter factor (CCC) as well as the required meter factor (DD) and pulse
duration (E) for the Pulse Divider according to
Table 8
and
Table 9
.
MMM indicates customer label.
q
p
CCC
[m³/h]
[imp/l]
[l/imp]
Divider
DD
[ms]
[ms] (E=4) [ms] (E=5) [ms] (E=6)
0.6
116
300
3.9
-
-
-
Default
0.6
1
300
33
-
20
50
100
0.6
2.5
750
63
-
-
-
100
1.5
119
100
3.9
-
-
-
Default
1.5
1
100
33
-
20
50
100
1.5
2.5
250
63
-
-
-
100
1.5
10
1000
34
-
-
-
100
2.5
198
60
3.9
-
-
-
Default
2.5
1
60
33
-
20
50
100
2.5
2.5
150
63
-
-
-
100
2.5
10
600
34
-
-
-
100
3.5
151
50
3.9
-
-
-
Default
3.5
1
50
33
-
20
50
-
3.5
2.5
125
63
-
-
-
100
3.5
10
500
34
-
-
-
100
3.5
25
1250
64
-
-
-
100
6
137
25
3.9
-
-
-
Default
6
1
25
33
-
20
50
-
6
2.5
62.5
63
-
-
-
100
6
10
250
34
-
-
-
100
6
25
625
64
-
-
-
100
10
178
15
3.9
-
-
-
Default
10
1
15
33
-
20
50
-
10
10
150
34
-
-
-
100
10
25
375
64
-
-
-
100
15
120
10
3.9
-
-
-
Default
15
1
10
33
-
20
-
-
15
10
100
34
-
-
50
100
15
25
250
64
-
-
-
100
15
100
1000
35
-
-
-
100
25
179
6
3.9
-
-
-
Default
25
1
6
33
-
20
-
-
25
10
60
34
-
-
50
100
25
25
150
64
-
-
-
100
25
100
600
35
-
-
-
100
Meter factor
Pulse duration
Table 8. Configuration options as to meter factor (DD) and pulse duration (E) for
Pulse Divider when connected to ULTRALFOW
®
54 or 34, q
p
0.6…25.