6.11.2.2.3
Mains supply cable
Pulse Transmitter/Pulse Divider is available with mains supply cable H03 VV-F for either 24 VAC or 230 VAC (l=1.5 m).
Figure 40. Mains supply cable (2 x 0.75 mm²), max 6 A fuse.
“
H03 VV-
F” is the designation of a strong PVC
mantle, which withstands max 70
C. Therefore, the mains cable must be
installed with sufficient distance to hot pipes, etc.
6.11.2.2.4
Cable screw connections
Cable dimension of signal
cable connections: 2…6 mm
Cable dimension of mains cable connections: 4.5…10 mm
Tightening torque: Maximum 4 Nm (traction relief minimum 40 N according to EN 61558)
<
In connection with battery supply, the unused cable screw connection must be sealed off as shown in
, page
6.11.2.2.5
Change of supply unit
The supply unit of Pulse Transmitter/Pulse Divider can be changed from mains supply to battery or vice versa as the needs
of the utility company change. Thus, it can be an advantage to change mains-supplied Pulse Transmitters/Pulse Dividers
to battery-supplied Pulse Transmitters/Pulse Dividers, e.g. in case of buildings under construction where the mains supply
can be unstable or periodically missing.
Note that the supply type appears from the label of Pulse Transmitter/Pulse Divider. If the original supply type is changed,
it will no longer be in accordance with the label.