10 Setup via front keys
A number of parameters in MULTICAL® 803 can be configured at the installation site. The
configuration is carried out via the SETUP loop, which is available as long as MULTICAL® 803
remains in transport state, or until the configuration is ended by activating “End setup”.
You can navigate from the USER loop to the SETUP loop by pressing the middle button (the
primary key) for 5 seconds until the text 1-USER appears on the display. Then use the arrow keys to
navigate to 3-SETUP and press the middle button once to open the SETUP loop in MULTICAL® 803.
Use the arrow keys to switch to the parameter that you want to change. You can reach these keys
by pressing the middle button. Then you can switch to the individual figures by pressing the arrow
keys, e.g. minutes under time (3-004). The parameter is set by pressing the primary button shortly
several times. Leave the menu item by keeping the primary key activated until “OK” is shown in
the display. After 4 minutes without activation of the front keys, the meter returns to the energy
reading in the USER loop.
12
SETUP loop
Index number in
display
1.0
Customer number (N
o
1)
3-001
2.0
Customer number (N
o
2)
3-002
3.0
Date
3-003
4.0
Time
1
3-004
5.0
Yearly target date 1 (MM.DD)
3-005
6.0
Monthly target date 1 (DD)
3-006
7.0
Flow sensor position: Inlet or outlet flow (A code)
3-007
8.0
Energy unit (B code)
3-008
9.0
Primary address module slot 1 (N
o
34)
3-009
10.0 Primary address module slot 2 (N
o
34)
3-010
11.0 Primary address module slot 3 (N
o
34)
3-011
12.0 Primary address module slot 4 (N
o
34)
3-012
13.0 Average time of min./max P and Q
3-013
14.0
q
hc
2
3-014
15.0 t offset
3-015
16.0 Radio “ON” or “OFF”
3-016
17.0 Input A1 (preset register)
3-017
18.0 Input B1 (preset register)
3-018
19.0 Meter number of Input A1
3-019
20.0 Meter number of Input B1
3-020
21.0 TL2
3-021
22.0 TL3
3-022
23.0 TL4
3-023
24.0 t5
3-024
25.0 EndSetup
3-025
1
The clock can, under the installation seal, be adjusted by all modules.
2
q
hc
can only be changed in meter type 6. Upon attempts to access this menu in other meter
types, the display shows the message “Off”.