MULTICAL® 803 & ULTRAFLOW®

6  Connection of power supply

6.1  Mains supply

MULTICAL® 803 is available with supply modules for either 24 VAC/VDC or 230 VAC.
MULTICAL® 803 can be supplied from either 24 VAC/VDC or 230 VAC with cable through the large 
cable connection to the left in the connection base. Use connecting cable with an outer diameter 
of 4-10 mm and ensure correct cable stripping as well as correct mounting of cable relief. If 
connecting to 230 VAC, it is important to make sure that the whole installation complies with 
current regulations. Kamstrup A/S can provide a supply cable to connect the mains supply, in the 
size 2 x 0.75 mm². The supply cable to the meter must never be protected by a larger fuse than 
permitted for any given cable size.
In case of doubt, it is recommended to take advice from an authorised electrician and get an 
individual assessment of the execution of the installation in question. In addition, note that work 
on fixed installations and any intervention in the fuse box must be carried out by an authorized 
electrician only.
For installation in Denmark: See “Installation of mains connected equipment for registration of 
consumption” from the Danish National Safety Board.

Replacement and extension of the mains supply

 

PLEASE MAKE SURE TO DISCONNECT THE MAINS SUPPLY FROM THE CONNECTION PCB 
BEFORE INITIATING THE REPLACEMENT OR EXTENSION OF THE SUPPLY!

The mains supply in MULTICAL® 803 consists of up to three supply modules of protection class 
II, which are connected to the underside of the connection PCB in the meter via a two-wire cable 
with connector at one end and screw terminals at the other. It is possible to connect 2 x 3.6 V 
supply modules to calculator and module slots as well as a 24 VDC supply module to the supply 
of analog outputs or passive third-party flow sensors. Read more in the technical description of 
MULTICAL® 803, document no. 5512-2360.

Note: 

Replacement and extension of the mains supply should always be carried out at a 
workshop.   

Содержание MULTICAL 803

Страница 1: ...Installation and user guide MULTICAL 803 ULTRAFLOW Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com...

Страница 2: ...X Electromagnetic environment Class E1 housing light industry and class E2 industry The meter s control cables must be drawn at min 25 cm distance from other installations Climatic environment Condens...

Страница 3: ...r supply 14 6 1 Mains supply 14 6 2 Backup battery 15 7 Testing of function 15 8 Info code 16 9 Communication modules 17 9 1 Module overview 17 9 2 Pulse inputs 17 9 3 Pulse outputs 18 9 4 Data pulse...

Страница 4: ...er pressure At a media temperature higher than 60 C the flow sensor should be shielded from unintended contact Please note that the following installation conditions must be obeyed Pressure stage ULTR...

Страница 5: ...ust neither be exposed to jerking nor pulling Please be aware of this when binding the cables and be careful not to pull the binders unnecessarily tight as this may damage the cables Please also note...

Страница 6: ...ep as possible into the pockets If a short response time is required non hardening thermally conductive paste can be used Push the plastic sleeve on the sensor cable into the sensor pocket and secure...

Страница 7: ...e flow sensor 3 1 Mounting of couplings and short direct sensor in flow sensor Flow sensor and any mounted blind plug can be used in connection with both PN16 and PN25 The flow sensor is available wit...

Страница 8: ...up to 45 downwards in relation to the pipe axis as shown above if required1 1 Flow sensor types 65 5 XXAX XXX 65 5 XXCX XXX and 65 5 XXJX XXX may also be turned 45 upwards Note In installations in wh...

Страница 9: ...o risk of air build up D Acceptable position in closed systems E Ought not to be placed immediately after a valve with the exception of block valves ball valve type which must be fully open when not u...

Страница 10: ...l provide the necessary electric coupling ULTRAFLOW MULTICAL ULTRAFLOW Inlet and outlet pipes are closely electrically coupled The parts of the pipe installation that are electrically connected to the...

Страница 11: ...d on the wall after which screws for these can be mounted 4 2 Compact mounting In some cases compact mounting of the MULTICAL 803 calculator may be an advantage The MULTICAL 803 calculator is large an...

Страница 12: ...t the supplied jumper on the pins marked with 2 W located directly above the screw terminals on the connection PCB If the supplied jumper is lost it is possible to terminate the extra connection termi...

Страница 13: ...nsors with transistor outputs Flow sensor Wire Terminal number V1 10 11 V2 69 11 MULTICAL 803 can be connected to other flow sensors with 24 V active pulse outputs by using connection PCB 6699 045 tha...

Страница 14: ...xecution of the installation in question In addition note that work on fixed installations and any intervention in the fuse box must be carried out by an authorized electrician only For installation i...

Страница 15: ...technical description of MULTICAL 803 document no 5512 2360 Optimal battery lifetime is obtained by keeping the battery temperature below 30 C e g by wall mounting The voltage of a lithium battery is...

Страница 16: ...oltage interrupted 2 The meter is supplied by the backup battery 3 minutes 9 External alarm e g via KMP 1 second 1 t1 above measuring range or switched off 3 minutes 1 t2 above measuring range or swit...

Страница 17: ...Wireless M Bus outputs Out C Out D 868 MHz HC 003 40 Analog outputs 2 x 0 4 20 mA HC 003 41 Analog inputs 2 x 4 20 mA 0 10 V HC 003 43 PQT Controller HC 003 60 LON TP FT 10 inputs In A In B HC 003 66...

Страница 18: ...s of the pulse outputs always follow the least significant digit displayed for energy and volume respectively 9 4 Data pulse inputs type HC 003 10 The data terminals are used for connection of e g a P...

Страница 19: ...condary and enhanced secondary addressing The module is connected to an M Bus master via terminals 24 and 25 using a twisted pair The polarity is without importance for the functionality The module is...

Страница 20: ...unlicenced frequency band in the 868 MHz area The radio module is available with either internal or external antenna Note that both antenna types use the same connection 9 11 Analog outputs type HC 0...

Страница 21: ...e module requires an external 24 VAC VDC power supply for operating the module and the connected sensors 9 13 PQT Controller type HC 003 43 The PQT Controller module with output for controlling of thr...

Страница 22: ...et MS TP pulse inputs type HC 003 66 BACnet is often used in building automation systems and industrial applications The BACnet module is compatible with ASHRAE 135 The module is BACnet certified and...

Страница 23: ...external antenna 32 current data registers are sent to the utility company every hour 24 7 365 and the module comes with an 8 year prepaid data subscription included It is possible to extend the subsc...

Страница 24: ...ry key activated until OK is shown in the display After 4 minutes without activation of the front keys the meter returns to the energy reading in the USER loop 12 SETUP loop Index number in display 1...

Страница 25: ...25 Kamstrup A S 55122412_A1_GB_2019 03 MULTICAL 803 ULTRAFLOW...

Страница 26: ...26 Kamstrup A S 55122412_A1_GB_2019 03 MULTICAL 803 ULTRAFLOW...

Страница 27: ...This reading indicates the connected flow sensor s nominal flow in m3 h Consumed energy in kWh MWh or GJ Press to see yearly and monthly log values Consumed cooling energy in kWh MWh or GJ Press to se...

Страница 28: ...Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com Kamstrup A S 55122412_A1_GB_2019 03 User Guide MULTICAL 803 ULTRAFLOW...

Отзывы: