Example of M-Bus network
It is possible to have more than one M-Bus Cascade unit in the same system, thereby
increasing the number of MULTICAL
®
energy meters.
All M-Bus Slaves can be read from point A.
From point B M-Bus Slaves in subnetworks 1 and 2 can be read.
From point C all M-Bus Slaves in subnetwork 2 can be read.
M-Bus
Cascade unit =
Total number of M-Bus Slaves
Total cable length
Master
Master
0.5/0.8 mm
2
1
0
40
1000/1800 m
1
38 + 40 = 78
2000/3600 m
2
38 + 38 + 40 = 116
3000/5400 m
3
38 + 38 + 38 + 40 = 154
4000/7200 m
4
38 + 38 + 38 + 38 + 40 = 192
5000/9000 m
5
38 + 38 + 38 + 38 + 38 + 40 = 230
6000/10800 m
6
38 + 38 + 38 + 38 + 38 + 38 + 22 = 250
7000/12600 m
Usefull numbers:
PcM-Bus software for Windows 98/2000/XP
S75-30-007
Table on number of M-Bus Slaves/cable lenght
as a function of the number of extension units