Venkon
Assembly, installation and operating instructions
42
Operating voltage [V]
120
230
Mains frequency [Hz]
60
50/60
Electrical supply [A / W]
0.29 / 15
0.17 / 16
Max. delivery volume 0 m / ft per hour [l / US
gal]
12 / 3.2
12 / 3.2
Max. delivery height [m / ft]
10 / 33
10 / 33
Noise level at a distance of 1 m / 3.3 ft
25
21
Operating mode
S1: Continuous operation
S1: Continuous operation
Protection class
II
II
Maximum output [kW / Btu/h]
9 / 30000
9 /30000
Max. water temperature [°C / °F]
40 / 104
40 / 104
Inner diameter of drain hose [mm / "]
6 / 1/4
6 / 1/4
Suction height [m / ft]
1 / 3.3
1 / 3.3
Tab. 7: Technical data for condensate pump
Potential-free alarm contacts, 3 A, normally closing, sound power for inductive loads 5 A at 230 V
Hall effect semiconductor-based level sensors, excellent safety
Integrated thermal cut-out
Fully sealed
Fuse 1 A (by others)
0
6
3
9
12
15
3
6
9
12
15
230 V
120 V
Flow rate [l/h]
Delivery height [m]
10 m*
- No suction height -
Fig. 41: Characteristic curves of the condensate pump
* Maximum recommended operating delivery height