Assembly, installation and operating instructions
20
6.4.1 Installation of basic unit
Example of basic unit EC, wall-mounted version, 4-pipe
Example of basic unit EC, ceiling-mounted version, 2-
pipe
15
Keyhole detail
Keyhole detail
15
1
There is no need for EC1M control
with electromechanical or external
control model.
Dimensions in brackets = model with cassette filter ePM10>50% (M5) / ePM1> 50% (F7)
Dimensions in brackets = model with cassette filter ePM10>50% (M5) / ePM1> 50% (F7)
1
There is no need for EC1M control
with electromechanical or external
control model.
Fig. 5: Suspension points for basic unit
A (Width of basic unit)
B (Distance of suspen-
sion points)
C (Rear wall)
D (Outlet opening)
Model 61
625
560
590
431
Model 63
925
860
890
731
Model 66
1375
1310
1340
1181
Model 67
1725
1660
1690
1531
Tab. 4: Dimensions of basic unit [mm]
when installing the basic units!
Highlight the dimensions and clearances of the key holes on the wall or ceiling as per the table, drill the holes and use
appropriate fixing materials to install the basic unit.
Align the basic unit for correct operation. Install the basic unit with a gradient on the condensation discharge side should
condensation be produced.
Once the basic unit has been aligned, prevent the fixing material from coming loose.