Katherm QK
Assembly, installation and operating instructions
33
Observe these points in the following installation diagrams for
Katherm QK
with KaControl:
Comply with the details on cable types and cabling with due consideration of VDE 0100.
Without *: NYM-J. The requisite number of wires, including PE conductor, is stated on the cable. Cross-sections are not
stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from high voltage lines.
With **: Lay UNITRONIC BUS LD 0.22 mm² or similar separately from high voltage lines.
If other types of cables are used, they must be at least equivalent.
Length of the BUS line from the KaController to unit 1: max. 30 m.
Maximum number of parallel units: 6 units. CANbus cards type 3260301 needed for each unit (see accessories) max-
imum 30 no.
Length of bus line from unit 1 to the last unit max. 30 m. The cable length can be increased to 300 m using CANbus
cards type 3260301 (see accessories).
The terminals on the unit for the mains power supply are suitable for a maximum wire cross-section of 2.5 mm².
We recommend type F when using RCCBs. Refer to the provisions of DIN VDE 0100 Parts 400 and 500 when configuring
the rated fault current.
Note the electrical data when rating the in-situ mains power supply and fuse (C16A, max.10 units, with the exception of
Katherm HK 320 E).
Содержание Katherm QK 190
Страница 2: ......
Страница 15: ...Katherm QK Assembly installation and operating instructions 15 6 2 1 Installation steps...
Страница 16: ...Katherm QK Assembly installation and operating instructions 16...
Страница 17: ...Katherm QK Assembly installation and operating instructions 17...
Страница 46: ...Katherm QK Assembly installation and operating instructions 46 13 Certificates...
Страница 50: ......
Страница 51: ......