36
2.55
ProtecTor
A new dimension in door screening
Installation and operating manual
8.3.6 KaControl
8.3.6.1 KaController installation
8.3.6.2 Connection of KaControl electronics
General information
• Route all low voltage lines along the shortest route.
• Ensure that low voltage and high voltage lines are separated, using metal
crossbars on cable harnesses.
• Use only shielded cables as low voltage and bus lines.
• Lay all bus lines in a linear pattern. Star-shaped wiring is not permitted!
• The KaController is connected via a bus connection to the respective
control board of the unit.
Electrical connection
• Connect the KaController to the nearest KaControl unit in line with the
layout plan. The maximum bus length between the KaController and the
KaControl master unit is 30 m.
• The respective KaControl unit automatically becomes the master unit in
the control circuit when a KaController is connected to it.
DIP switch setting
The dip switches on the rear of the KaController should be set as per the
figure:
• Dip switch 1: ON
• Dip switch 2: OFF
Installation of flush box
KaController terminals
Dip switch setting on the KaController
Laying of bus cables