4 Installation
4.1 Installation example
D
E
SD0000063
B
C
A
F
Item
Description
A
Combi Port E D
B
Room temperature controller
C
Port Base
D
Heating supply (primary)
E
Heating return (primary)
F
Cold water from riser (CW)
The above installation example shows a typical installation with
Combi Port E with tap water and underfloor heating manifolds.
A Uponor Smatrix controller for room temperature control is mounted
and connected to the manifold.
4.2 Heat interface unit view
Note
The insulation should never be removed from the unit!
SI00000398
The illustrations in the following installation steps describe the
process with Combi port E D-UFH unless nothing else is mentioned.
The insulation mounted in the unit is removed in the illustrations only
to show all components and increase the understanding.
The installation of Combi Port E D-X is performed in the same way.
4.3 Heat interface unit with UFH
manifold
Install the wall bracket
Note
See the dimensional drawings for measurements. Pay
attention to the horizontal alignment.
Note
Consider the height from the floor surface to ensure that
there is space left for the installation of underfloor heating
manifold.
SI0000318
A
B
Item
Description
A
Plug (4 pcs)
B
Hexagon bolt (4 pcs)
1.
Mark the hole positions on the wall and drill holes using a
6 mm
drill.
2.
Insert the plugs in the drilled holes.
3.
Attach the wall bracket to the wall using the hexagon bolts.
Combi Port E D
|
Installation and operation manual
|
9